Start and stop events

  • Last UpdatedJan 23, 2025
  • 2 minute read

Events are read from the BatchIDLog and BatchDetail tables. The InBatch system can optionally provide status for Batch, Unit, and Phase level states by specifying the EnableAllStates parameter. For more information, see Command-line parameter reference.

An event read from the BatchDetail table must have the UnitOrConnection information available for the interface to process and associate it with the unit. If the UnitOrConnection information is empty, the interface does not know which unit to associate the event with and waits for another event with more information.

PIBatch/Procedure

Supported PI Batch/Procedure start codes

Action code

Action description

Event level

201

Batch received Start

Batch

Supported PI Batch/Procedure end codes

Action code

Action description

Event level

205

Batch set Done

Batch

206

Batch set Closed

Batch

209

Batch set Aborted

Batch

PIUnitBatch/Unit Procedure

Supported PI UnitBatch/Unit Procedure start codes

Action code

Action description

Event level

500

Unit Procedure received Run

Unit Procedure

Supported PI UnitBatch/Unit Procedure end codes

Action code

Action description

Event level

501

Unit Procedure received Done

Unit Procedure

Operation

Supported PI Operation start codes

Action code

Action description

Event level

502

Operation received Run

Operation

Supported PI Operation end codes

Action code

Action description

Event level

503

Operation received Done

Operation

Phase

Supported PI Phase start codes

Action code

Action description

Event level

223

WAIT FOR ENTRY ACK

Phase

224

Receive Entry ACK

Phase

226

Receive Ready

Phase

227

Start

Phase

241

Wait for Req Edits

Phase

243

Wait for Req Cmmt

Phase

The start time of a phase should be represented by the first occurrence of any supported phase start codes listed in the "Supported PI Phase start codes" table.

Supported PI Phase end codes

Action code

Action description

Event level

233

Received Aborted

Phase

234

Received Done

Phase

235

Reset Phase

Phase

239

Received Bad Ready

Phase

415

Done

Phase. If Collect415 is enabled, then this also sends Phase Start.

The end time of a phase should be represented by the first occurrence of any supported phase end codes listed in the "Supported PI Phase end codes" table. Action code 415 acts as a normal phase close if flag Collect415 Is disabled. If flag Collect415 is enabled then:

  • If a Phase close already exists, the interface will do nothing to the phase

  • If a Phase does not exist, then the interface will create a zero duration phase event with one phase state child "DONE".