Resolved issues
This table describes important resolved issues in AVEVA Application Server 2023 R2 P01. Some issues that have been fixed in this release may not be listed.
|
Original Issue |
Related Issues |
Case/SR Number |
Description |
|
2985894 |
960354373 |
When using the warm redundancy option, the aaCALWrap.exe process consumed a great deal of memory. |
|
|
3018396 |
960341870 |
In some cases, after failover from the primary server to the backup server, some shelved alarms did not show in the shelved alarm list. The status of these alarms was still "shelved," they just did not appear when listing shelved alarms. |
|
|
3023716 |
960375402 |
In a Multi-Galaxy configuration, the warning message was logged continuously on the GR node. This happened because the passphrase solution could not be found. |
|
|
3039913 |
960380498 |
When System Platform was installed in a non-default location, such as on the D: drive, deploying WinPlatforms caused errors and warnings in the log and the platforms were not available in the OCMC Platform Manager. |
|
|
3040483 |
960381315 |
Importing objects via a package (.aaPKG) file incremented the objects' versions by two steps. |
|
|
3046335 |
960376548 |
Alarms which did not return to normal for a very long time (approximately one month) appeared in Historian with a negative duration. |
|
|
3067809 |
960390378 |
Improved performance when deleting objects. |
|
|
3081734 |
960352243 |
Objects that were set to Scan on Demand were not always added to the list for OI Server. As a result, these items were sometimes not scanned. |
|
|
3109688 |
960387634 |
GRAccess could not write to any attribute that had a description field. Therefore, it could not create any object that contained any attribute with a description field. |
|
|
3166242 |
960392759 |
In a warm redundancy configuration, after failover occurred, the EngineObjects[] attribute no longer contained a list of deployed objects. |
|
|
3198388 |
960395617 |
When deploying an OMI ViewApp that included object wizards, the PCS Framework used more than 90% of the server's CPU. |
|
|
3201271 |
960390809 |
If a galaxy was backed up using the Operations Control Management Console (OCMC), then a new galaxy was created from the backup, you could no longer connect to the original galaxy. |
|
|
3242289 |
960400382 |
Collecting diagnostic information using the default configuration could create an unlimited number of files in the ArchestrA temp folder. |
|
|
3259264 |
960403401 |
If an exported CSV file contains two objects which have attributes with the same name but different types (for example, one is Boolean and the other is a string), trying to import the CSV file fails with an error message. |
|
|
3260947 |
960396305 |
Low priority alarms were being historized even though the galaxy was configured not to do so. |
|
|
3261424 |
960404170 |
If you created an instance from a master template, then changed the default settings for an object wizard in the master template, you could not edit the instance or export it to a CSV file. |
|
|
3264570 |
960404338 |
If the input source and output destination for an attribute associated with an object wizard were different, the output destination was set to --- if a change was made to the object template. This occurred even if the attribute was created in the object instance and did not exist in the template. |
|
|
3270224 |
960405891 |
Importing a package file containing a graphic with multiple client controls which used the same dependent DLLs failed. |
|
|
3270262 |
960405918 |
With multiple people using the IDE at the same time, the aaGR service crashed every 15 to 25 minutes. |
|
|
3270629 |
3065034 |
960390172 |
Enabling the System Management Server slows down log in to OMI ViewApps at runtime. |
|
3278545 |
960407805 |
Longer than expected time to failover from one server to another caused unacceptably long gaps in historized data. |
|
|
3279907 |
960407298 |
There was a small memory leak in the module aaGlobalDataCacheMonitorSrv. Eventually, this caused the following warning to be written to the log repeatedly: . As the memory leak was very small, it could take several months before this warning appeared. |
|
|
3281737 |
960406315 |
Post-upgrade from System Platform 2023 P02 to System Platform 2023 R2, AVEVA.IOMBLS.ServiceHost.exe caused memory leak and then stopped responding. |
|
|
3282637 |
960407900 |
When using the Assign to option to assign an object to an area, typing in the list box the on the dialog did not move the list to match your entry. |
|
|
3293455 |
None |
Validating a large object sometimes caused a System.OutOfMemoryException and could cause the IDE to crash. For example, this could happen when migrating a galaxy that contained large objects. |
|
|
3303557 |
960411247 |
The I/O Mapping view showed attributes for an instance even if those attributes were excluded by object wizard choices. |
|
|
3318750 |
960391528 |
Closing and reopening the IDE caused deployed VIewApps to incorrectly show that they needed to be redeployed, even though they had not changed. |
|
|
3324307 |
960417221 |
Checking in changes to a template and propagating the changes to its children could take hours and then fail, even though the IDE showed that it had completed successfully. When this occurred, the template remained checked out and error messages were written to the logger, starting with something like: Error WWCdi Error 80040E14: Description 'Violation of PRIMARY KEY constraint 'PK__#trimatt__38174EC39114E2BF'. Cannot insert duplicate key in object 'dbo.#trimattr'. The duplicate key value is (512616, 1041602300). Line:308, Store proc:internal_ow_streamline_dynamic_a appeared |