AVEVA™ PI Server 2018 SP3 Patch 6 includes updates to the following components:

  • Data Archive 2018 SP3 Patch 4

  • PI AF Server 2018 SP3 Patch 5

  • PI Notifications Service 2018 SP3 Patch 4

  • PI AF Client 2018 SP3 Patch 5

There are no new features in this release. For more information on system requirements for PI Server 2018 SP3 Patch 6, visit the AVEVA Support portal.

Fixes and enhancements

The table lists all resolved issues in this release.

Product/Component

WI / PLI

Description

Asset Framework

27763 / 70108

XML import fails to complete for templated analyses.

Data Archive (Archive)

94917

The Data Archive message ID 2255 can occasionally display timestamps inaccurately. To address this issue, the first event and the last event timestamp will now be correctly logged.

Data Archive (Archive)

94921

Data Archive has been fixed to reload registered archives when it encounters a network issue with error number 59.

Data Archive (Archive)

94923

An add event (Addevent) message failure will now correctly set the throttling limit to a max of 10 per 120 seconds.

Data Archive (Backup)

94919

An unneeded quote in the PI Server batch utility (pibackup.bat) was removed on line 303.

Data Archive (Backup)

94924

Privileges for backup are correctly set during install and upgrade time. Previously some of the settings were incorrect.

Data Archive (Message)

94918

A memory leak issue has been resolved.

Data Archive (Message)

94927

A message subsystem failure has been resolved.

Data Archive (pictrdll)

94926

Error messages are no longer logged on request for non-existent counters.

Data Archive (PINetmgr)

94922

Upon startup, if PINetmgr is unable to register an Server Principal Name (SPN), it will retry every 5 seconds up to a specified amount of time. The default is 30 seconds (as specified in the PITimeout table).

Data Archive (PINetmgr)

76804

In rare cases, it is possible for PI Data Archive to assign an incorrect PI Identity to a connection.

PI Notifications Service

27266

A memory leak issue has been resolved.

Upgrade compatibility considerations

The following items are known issues in this release.

  • If you are using PI Asset Framework to store complex types in AFValue and ExtendedProperties, some functionality may be lost initially on upgrade. This can be remediated by setting enableBinaryFormatter to ‘True’ in the AFSDK.config on PI Clients.

    Note: Additional security protection was added that disables use of the BinaryFormatter. The 'enableBinaryFormatter' setting should be discouraged.

  • The AFElement.GetAttributeValues and AFEventFrame.GetAttributeValues methods allow an optional WindowsIdentity/ClaimsIdentity to be passed in so that a service, using a trusted subsystem model, can evaluate access for the specified user identity. However, if the service is not mapped to the Administrator Identity on the PI Asset Framework server, the identity parameters are ignored, and the attributes and data are returned with the access rights of the caller (the trusted subsystem). This may result in granting Read Data privilege to the attributes to the end-user. The work around is to run the trusted subsystem service with admin rights on the PI System. This issue only affects applications that are trying to impersonate calls to users, such as the PI SQL Data Access Server (Real-Time Query Processing Engine).

  • If you want to use PI SQL Data Access Server (RTQP Engine) with PI Server 2018 SP3 Patch 6, you must upgrade or install PI SQL Data Access Server (RTQP Engine) 2023 SP1. For more information on PI SQL Data Access Server (RTQP Engine), see PI SQL Data Access Server (RTQP Engine) 2023.

Refer to the AVEVA Customer Portal Products page for a complete list of known issues.

Security information and guidance

We are committed to releasing secure products. This section is intended to provide relevant security-related information to guide your installation or upgrade decision.

We proactively disclose aggregate information about the number and severity of security vulnerabilities addressed in each release. The tables below provide an overview of security issues addressed and their relative severity based on standard scoring.

Vulnerabilities fixed

The following table lists the number of fixed vulnerabilities in this release by severity category and CVSS base score range.

Severity category

CVSS base score range

Number of fixed vulnerabilities

Critical

9.0 - 10

0

High

7.0 - 8.9

1

Medium

4.0 - 6.9

1

Low

0 - 3.9

0

Vulnerabilities mitigated

Additional security protection was added that disables use of the BinaryFormatter. The 'enableBinaryFormatter' setting should be discouraged.

Distribution kits

The following table provides the list of products included in the distribution kits for this release.

Product

Software version

Microsoft Visual C++ 2022 Redistributables (x86 and x64)

14.34.32532

Microsoft VSTO 2010 Runtime

10.0.60724

OSIsoft MS VB Runtime Redistributables

1.0.1

PI Buffer Subsystem

4.9.0.37

PI Network Subsystem

3.4.450.165

PI AF Client

2.10.11.2717

PI AF Server

2.10.11.2717

PI Analysis Service

2.10.6.195

PI Notifications Service

2.10.11.2697

PI Data Archive

3.4.450.165

PI Software Development Kit (PI SDK)

1.4.7.620

PI System Management Tools

3.6.3.65

PI Collective Manager

1.4.3.25

PowerShell Tools for the PI System

2.2.2.91

PI Module Database Builder

1.3.0.0

©2023 AVEVA Group plc and its subsidiaries. All rights reserved.

In This Topic
TitleResults for “How to create a CRG?”Also Available in