Parameter |
Description |
|---|---|
|
/c1 Optional |
Location1 point attribute override. Load all points configured for the specified point source regardless of Location1 and interface ID values. |
|
/c2=# Optional |
Location2 point attribute override. Ignore Location2 for each point and use the specified value. Valid values are 0-7. |
|
/c3=# Optional |
Location3 point attribute override. Ignore Location3 for each point and use the specified value. Valid values are 0-31. |
|
/c4=# Optional |
Location4 point attribute override. Ignore Location4 for each point and use the specified value. Valid values are:
|
|
/c5=# Optional |
Location5 point attribute override. Ignore Location5 for each point and use the specified value. Valid values are 0-5. |
|
/ptid Optional |
Point ID of source PI point is specified in UserInt1 attribute. Ignore InstrumentTag, ExDesc, and Tag (PI point name) attributes. Note: This switch is not compatible with source Data Archive failover because point IDs will not necessarily match between source Data Archives. If the source Data Archives are part of a PI collective use /tn instead. |
|
/tn Optional |
Source point name is same as interface point name. Ignore InstrumentTag, ExDesc and UserInt1 attributes. |
|
/tnex Optional |