Edge Data Store

Supported features

  • Last UpdatedSep 26, 2025
  • 7 minute read

The Modbus TCP EDS (Edge Data Store) adapter collects data using register types and then converts the registers into data types. It can apply bitmaps and data conversion to values converted from reading the Modbus TCP devices.

Definition: Modbus TCP, Transmission Control Protocol, is a Modbus variant used for communications over TCP/IP networks, connecting over port 502. It does not require a checksum calculation, as lower layers already provide checksum protection.

Definition: Modbus TCP, Transmission Control Protocol, is a Modbus variant used for communications over TCP/IP networks, connecting over port 502. It does not require a checksum calculation, as lower layers already provide checksum protection.

Modbus Security

The Modbus TCP EDS adapter supports secure Modbus communication over TLS in accordance with the Modbus TCP/Security specification.

Register types

The Modbus TCP EDS (Edge Data Store) adapter supports 6 register types, corresponding to 4 function codes (1-4). Since one function code can return two types of registers, either 16-bit or 32-bit depending on the device, either the register type or the register type code is required when configuring the data selection for the adapter.

Definition: Modbus TCP, Transmission Control Protocol, is a Modbus variant used for communications over TCP/IP networks, connecting over port 502. It does not require a checksum calculation, as lower layers already provide checksum protection.

The following table lists all the register types supported in the Modbus TCP EDS (Edge Data Store) adapter.

Definition: Modbus TCP, Transmission Control Protocol, is a Modbus variant used for communications over TCP/IP networks, connecting over port 502. It does not require a checksum calculation, as lower layers already provide checksum protection.

Register Type

Register Type Code

Description

Function Code

Coil

1

Read Coil Status

1

Discrete

2

Read Discrete Input Status

2

Holding16

3

Read 16-bit Holding Registers

3

Input16

6

Read 16-bit Input Registers

4

When reading from function codes 1 and 2, the adapter expects these to be returned as single bits. For function codes 3 and 4, the adapter expects 16 bits to be returned from devices that contain 16-bit registers and 32 bits to be returned from devices that contain 32-bit registers.

Data types

The Modbus TCP EDS (Edge Data Store) adapter converts readings from single or multiple registers into the data types specified by the data type code and populates the value into streams created in the Edge Data Store (EDS (Edge Data Store)).

Definition: Modbus TCP, Transmission Control Protocol, is a Modbus variant used for communications over TCP/IP networks, connecting over port 502. It does not require a checksum calculation, as lower layers already provide checksum protection.

The following table lists all data types with their corresponding type codes supported by the Modbus TCP EDS (Edge Data Store) adapter.

Definition: Modbus TCP, Transmission Control Protocol, is a Modbus variant used for communications over TCP/IP networks, connecting over port 502. It does not require a checksum calculation, as lower layers already provide checksum protection.

Data type code

Data type name

Value type

Register type

Description

1

Boolean

Boolean

Bool

0 = false
1 = true

10

Int16

Int16

Bool/16-bit

Read 1 Modbus TCP register and interpret as a 16-bit integer. Bytes [BA] read from the device are stored as [AB].

Definition: Modbus TCP, Transmission Control Protocol, is a Modbus variant used for communications over TCP/IP networks, connecting over port 502. It does not require a checksum calculation, as lower layers already provide checksum protection.

20

UInt16

UInt16

Bool/16-bit

Read 1 Modbus TCP register and interpret as an unsigned 16-bit integer. Bytes [BA] read from the device are stored as [AB].

Definition: Modbus TCP, Transmission Control Protocol, is a Modbus variant used for communications over TCP/IP networks, connecting over port 502. It does not require a checksum calculation, as lower layers already provide checksum protection.

30

Int32

Int32

16-bit/32-bit

Read 32 bits from the Modbus TCP device and interpret as a 32-bit integer. Bytes [DCBA] read from the device are stored as [ABCD].

Definition: Modbus TCP, Transmission Control Protocol, is a Modbus variant used for communications over TCP/IP networks, connecting over port 502. It does not require a checksum calculation, as lower layers already provide checksum protection.

31

Int32ByteSwap

Int32

16-bit/32-bit

Read 32 bits from the Modbus TCP device and interpret as a 32-bit integer. Bytes [BADC] read from the device are stored as [ABCD].

Definition: Modbus TCP, Transmission Control Protocol, is a Modbus variant used for communications over TCP/IP networks, connecting over port 502. It does not require a checksum calculation, as lower layers already provide checksum protection.

40

UInt32

Int32

16-bit

Read 32-bits from the Modbus TCP device and interpret as a 32-bit unsigned integer. Bytes [DCBA] read from the PLC are stored as [ABCD].

41

UInt32ByteSwap

Int32

16-bit

Read 32-bits from the Modbus TCP device and interpret as a 32-bit unsigned integer. Bytes [BADC] read from the PLC are stored as [ABCD].

100

Float32

Float32

16-bit/32-bit

Read 32 bits from the Modbus TCP device and interpret as a 32-bit float. Bytes [DCBA] read from the device are stored as [ABCD].

Definition: Modbus TCP, Transmission Control Protocol, is a Modbus variant used for communications over TCP/IP networks, connecting over port 502. It does not require a checksum calculation, as lower layers already provide checksum protection.

101

Float32ByteSwap

Float32

16-bit/32-bit

Read 32 bits from the Modbus TCP device and interpret as a 32-bit float. Bytes [BADC] read from the device are stored as [ABCD].

Definition: Modbus TCP, Transmission Control Protocol, is a Modbus variant used for communications over TCP/IP networks, connecting over port 502. It does not require a checksum calculation, as lower layers already provide checksum protection.

110

Float64

Float64

16-bit/32-bit

Read 64 bits from the Modbus TCP device and interpret as a 64-bit float. Bytes [HGFEDCBA] read from the device are stored as [ABCDEFGH].

Definition: Modbus TCP, Transmission Control Protocol, is a Modbus variant used for communications over TCP/IP networks, connecting over port 502. It does not require a checksum calculation, as lower layers already provide checksum protection.

111

Float64ByteSwap

Float64

16-bit/32-bit

Read 64 bits from the Modbus TCP device and interpret as a 64-bit float. Bytes [BADCFEHG] read from the device are stored as [ABCDEFGH].

Definition: Modbus TCP, Transmission Control Protocol, is a Modbus variant used for communications over TCP/IP networks, connecting over port 502. It does not require a checksum calculation, as lower layers already provide checksum protection.

1001 - 1250

String

String

16-bit/32-bit

1001 reads a one-character string, 1002 reads a two-character string, and 1003 reads a three-character string and so on. Bytes [AB] are interpreted as "AB".

2001 - 2250

StringByteSwap

String

16-bit/32-bit

2001 reads a one-character string, 2002 reads a two-character string, and 2003 reads a three-character string and so on. Bytes [BA] are interpreted as "AB".

Apply bitmap

The Modbus TCP EDS (Edge Data Store) adapter supports applying bitmaps to the value converted from the readings from the Modbus TCP devices. A bitmap is a series of numbers used to extract and reorder bits from a word register. The format of the bitmap is uuvvwwxxyyzz, where uu, vv, ww, yy, and zz each refer to a single bit. A leading zero is required if the referenced bit is less than 10. The low-order bit is 01 and high-order bit is either 16 or 32. Up to 16 bits can be referenced for a 16-bit word (data types 10 and 20) and up to 32 bits can be referenced for a 32-bit word (data type 30 and 31). For example, the bitmap 0307120802 maps the second bit of the original word to the first bit of the new word, the eighth bit to the second bit, the twelfth bit to the third bit, and so on. The high-order bits of the new word are padded with zeros if they are not specified.

Definition: Modbus TCP, Transmission Control Protocol, is a Modbus variant used for communications over TCP/IP networks, connecting over port 502. It does not require a checksum calculation, as lower layers already provide checksum protection.

Definition: Modbus TCP, Transmission Control Protocol, is a Modbus variant used for communications over TCP/IP networks, connecting over port 502. It does not require a checksum calculation, as lower layers already provide checksum protection.

Not all data types support applying bitmap. The data types supporting bitmap are:

  • Int16 (Data type code 10)

  • UInt16 (Data type code 20)

  • Int32 (Data type code 30 and 31)

Apply data conversion

The Modbus TCP EDS (Edge Data Store) adapter supports applying data conversion to the value converted from reading the Modbus TCP devices. A conversion factor and conversion offset can be specified. The conversion factor is used for scaling the value up or down, and the conversion offset is used for shifting the value. The mathematical equation used in conversion is the following:

Definition: Modbus TCP, Transmission Control Protocol, is a Modbus variant used for communications over TCP/IP networks, connecting over port 502. It does not require a checksum calculation, as lower layers already provide checksum protection.

Definition: Modbus TCP, Transmission Control Protocol, is a Modbus variant used for communications over TCP/IP networks, connecting over port 502. It does not require a checksum calculation, as lower layers already provide checksum protection.

<After Conversion> = <Before Conversion> / Factor - Offset

Not all data types support applying data conversion. Data types that support data conversion are:

  • Int16 (Data type code 10)

  • UInt16 (Data type code 20)

  • Int32 (Data type code 30 and 31)

  • Float32 (Data type code 100 and 101)

The value with data conversion applied will always be converted to the 32-bit float type to maintain the precision of the conversion factor and conversion offset.