Please ensure Javascript is enabled for purposes of website accessibility
Powered by Zoomin Software. For more details please contactZoomin

PI Interface for Siemens SIMATIC Batch

SIMATIC batch start and stop events

  • Last UpdatedFeb 05, 2025
  • 2 minute read

For any level, start is indicated by events in which the Event field contains "System" and the Value field contains "Start". End is indicated by events in which the Event field contains "System" and the Value field contains "End". Phase states start when the Event field contains "State Change" and Level = 4 (phase). Phase states stop when the next phase state begins or when the parent phase ends.

Recipe data is read from events in which the Event field contains "Recipe Header", and the process data is read from events where Event field contains "Act_Val" or "SetPoint". The following table describes the data that accompanies events read from the data source.

Event Field

Meaning

Optional or Required

Level (hidden)

  • Batch

  • Unit Procedure

  • Operation

  • Phase

Required, hidden

Time

GMT Timestamp of the event in "yyyy-MM-dd hh:mm:ss.000" format

Required

UniqueID

Unique ID of the PI Batch (= Simatic Batch "Batch ID")

Required

BatchID

Batch ID of the PI Batch (=Simatic Batch "Batch Name")

Required

Procedure

Name of the recipe

Required

UnitProcedure

Name of the unit procedure with activation counter in [ ] as suffix

Level 1: Empty

Level 2, 3, 4: Required

Operation

Name of the Operation with activation counter in [ ] as suffix

Level 1, 2: Empty

Level 3, 4: Required

Phase

Name of the Phase, with activation counter in [ ] as suffix

Level 1, 2, 3: Empty

Level 4: Required

Category

Available Category field values:

  • ProcessInput

  • ProcessOutput

  • ProcessParameter

Required for parameter event (in Event field)

Act_Val

SetPoint

Descript

Depends on contents of Event field as follows:

  • StateChange: new state

  • Act_Val or SetPoint: process parameter name

  • Recipe Header: recipe parameter name

Required for parameter event (in Event field):

  • Act_Val

  • SetPoint

  • Recipe Header

  • StateChange

Event

Indicates nature of event as follows:

  • Batch start / end data: System

  • Batch / recipe header data: Recipe Header

  • State change events: StateChange

  • Process parameter data: Act_Val or SetPoint

Required

Value

Depends on contents of Event field as follows:

  • StateChange: integer value of the new state

  • Act_Val or SetPoint: process parameter value

  • Recipe Header: recipe parameter value

  • System: Start or End

Required

Eu

Engineering units. Depends on contents of Event field as follows:

  • Act_Val or SetPoint: process parameter engineering units

  • Recipe Header: recipe parameter engineering units

Optional

Area

First level of equipment structure in PI Batch

Optional

ProcessCell

Second level of equipment structure in PI Batch

Optional

Unit

Name of the unit module for PI Batch equipment structure (Simatic Batch unit name)

Level 1: empty

Level 2, 3, 4: required

Operation Module

Name of the operation module for PI Batch equipment structure (Simatic Batch operation name)

Level 1, 2: empty

Level 3, 4: required

PhaseModule

Name of the phase module for PI Batch equipment structure (Simatic Batch phase name)

Level 1, 2, 3: empty

Level 4: required

MaterialName

Name of the material

Required for Parameter Event:

Act_Val

SetPoint

All others empty

MaterialID

ID of the material

Required for Parameter Event:

Act_Val

SetPoint

All others empty

TitleResults for “How to create a CRG?”Also Available in