OPC UA Historical Data
- Last UpdatedOct 29, 2026
- 1 minute read
The OPC UA user must have HistoryRead access to the variables the connector uses to retrieve historical data. Verify that the UserAccessLevel attribute includes HistoryRead for the user account that the connector uses to access the OPC UA server.
The following table provides settings and definitions for historical data options:
|
Settings |
Definitions |
|---|---|
|
[x] Enable History Recovery |
Marking this initiates the history recovery every time connector communication to an OPC UA server is broken and then re-established, and every time the connector is stopped and restarted. The history recovery is implemented for those OPC UA dynamic variables that have a history to recover. |
|
Read Block Size [10] |
Specifies the maximum number of variables in the history Read() call. |
|
Number of Values per Node [ 0 ] |
Specifies the maximum number of returned events per variable in the history Read() call. 0 means the server returns the maximum number of values per node. |
|
[x] Include variables having historical data only |
Marking this causes the connector to scan those OPC UA variables that store only historical data; that is, variables without current values. Note: When marked, the Historical Data Scan Period is used for polling. |
|
Historical Data Scan Period [s] [ 60 ] |
Specifies the scan period used for polling variables with historical data. |