OPC UA Historical Data
- Last UpdatedJun 10, 2025
- 1 minute read
The following table provides settings and definitions for historical data options:
|
Settings |
Definitions |
|---|---|
|
[x] Enable History Recovery |
Marking this initiates the history recovery every time connector communication to an OPC UA server is broken and then re-established, and every time the connector is stopped and restarted. The history recovery is implemented for those OPC UA dynamic variables that have a history to recover. |
|
Read Block Size [10] |
Specifies the maximum number of variables in the history Read() call. |
|
Number of Values per Node [ 0 ] |
Specifies the maximum number of returned events per variable in the history Read() call. 0 means the server returns the maximum number of values per node. |
|
[x] Include variables having historical data only |
Marking this causes the connector to scan those OPC UA variables that store only historical data; that is, variables without current values. Note: When marked, the Historical Data Scan Period is used for polling. |
|
Historical Data Scan Period [s] [ 60 ] |
Specifies the scan period used for polling variables with historical data. |