If the interface consistently misses scans, it is probably attempting to retrieve values from SNMP devices that are not readily accessible. For example, PI SNMP is collecting data for

  • 100 points from device 1

  • 100 points from device 2

  • 100 points from device 3

  • 100 points from device 4

  • 100 points from device 5

If device 3 is removed from the network, PI SNMP still polls this device for the associated points, using a default timeout of 3000 milliseconds and 3 retries. Thus, scans will be missed.

To improve this condition, try changing one or more of the startup command parameters:

  • decrease the number of retries (-retries)

  • decrease the timeout interval (-timeout)

  • decrease the number of consecutive timeouts (-cto).

For example,

pisnmp.exe -retries=0 -timeout=1000 -cto=1