Application Server
|
Port |
Can be configured |
Protocol |
Subsystem |
Purpose |
|---|---|---|---|---|
|
135 |
No |
TCP |
Bootstrap |
RPC |
|
139 445 |
No |
TCP |
Bootstrap |
NetBios |
|
443 |
No |
TCP (HTTPS) |
AVEVA.AppServer. BootstrapProxy.exe |
AVEVA.AppServer. BootstrapProxy.exe |
|
808 |
Yes |
TCP |
Multi-Galaxy |
Galaxy Pairing ASBAuthentication Service ASBGRBrowsing Service IOM BLS Service ASMBMxDataProvider Service |
|
5026 |
Yes |
TCP |
NMXSVC |
NMXSVC |
|
8090 |
Yes |
TCP |
aaGR |
aaGR |
|
30000 30001 |
Yes |
TCP/UDP TCP |
Bootstrap, Redundancy PMC |
Local redundancy messaging (WinPlatform) |
|
32568 |
Yes |
TCP |
aaEngine.exe |
aaEngine.exe |
|
48031 |
Yes |
TCP |
Platform Common Services |
OPC UA Server |
|
49152 – 65535 |
No |
TCP |
aaPIM |
DCOM |
AVEVA Historian
|
Port |
Can be configured |
Protocol |
Subsystem |
Purpose |
|---|---|---|---|---|
|
32565 |
Yes |
TCP |
aaClientAccessPointNG.exe |
Historian Client Access Point NG |
|
32568 |
Yes |
TCP |
AVEVA Historian |
AVEVA Historian as a real-time service |
|
32569 |
Yes |
TCP (HTPPS) |
Insight |
Insight on-premise gateway |
|
32573 |
Yes |
TCP (HTTPS) |
Historian Secured Gateway |
REST communications |
Device Integration (Communication Drivers Pack)
|
Port |
Can be configured |
Protocol |
Subsystem |
Purpose |
|---|---|---|---|---|
|
102 |
No |
TCP |
SiDirect OI Server |
Siemens PLC communication to OI Server |
|
135 |
No |
TCP |
DASEngine, OPC |
DCOM and RPC |
|
443 |
Yes |
TCP (HTTPS) |
GDIWebServer |
MQTT and Auto-Build configuration |
|
502 |
No |
TCP |
MBTCP OI Server |
Modbus communication to OI Server |
|
1883 8883 |
Yes |
TCP |
MQTT |
MQTT broker communication to OI Server |
|
2221 2222 2223 |
No |
TCP |
ABTCP OI Server |
Allen-Bradley PLC communication to OI Server |
|
5413 |
No |
TCP |
SuiteLink |
SuiteLink communication |
|
18245 |
No |
TCP |
GESRTP OI Server |
GE PLC communication to OI Server |
|
44818 |
No |
TCP |
ABCIP OI Server |
Allen-Bradley CIP PLC communication to OI Server |
|
See note, below |
Yes |
TCP |
OPC UA Services |
Remote access to the OPC UA servers |
Note: The Communication Drivers Pack uses the default OPC ports, which are are configurable.
For details, refer to the OPC Foundation documentation:
https://opcfoundation.github.io/UA-.NETStandard/help/firewall_settings.htm
InTouch
|
Port |
Can be configured |
Protocol |
Subsystem |
Purpose |
|---|---|---|---|---|
|
51218 |
No |
TCP |
Alarmmgr.exe |
Alarm Manager |
|
48032 – 65000 |
Yes |
TCP |
InTouch.OPCUA.ServiceHost.exe |
InTouch OPC UA |
InTouch Access Anywhere (ITAA)
|
Port |
Can be configured |
Protocol |
Subsystem |
Purpose |
|---|---|---|---|---|
|
443 |
Yes |
TCP |
EricomSecureGateway.exe |
Secure Gateway |
|
7433 |
Yes |
TCP |
EricomAuthenticationServer.exe |
Access Anywhere Authentication Server |
|
8080 |
Yes |
TCP |
EricomSecureGateway.exe AccessServer64.exe |
Communication between ITAA Server and ITAA Secure Gateway |
|
57111 |
No |
UDP |
EricomSecureGateway.exe |
Secure Gateway |
|
57733 57734 57735 |
No No No |
TCP |
AccessServer64.exe |
Server |
Licensing
|
Port |
Can be configured |
Protocol |
Subsystem |
Purpose |
|---|---|---|---|---|
|
80 |
Yes |
TCP (HTTP) |
License Manager |
Web Service |
|
443 |
Yes |
TCP |
License Manager |
License Manager outbound to activation server |
|
50051 |
Yes |
TCP (HTTPS) |
Licensing Platform |
Serve licensing requests from products |
|
55555 |
Yes |
TCP (HTTP) |
License Server |
License Server Translator service. Also required to support prior client versions from Server 4.0 |
|
55559 |
Yes |
TCP (HTTP/ HTTPS) |
License Server |
License Server core service |
|
59200 |
Yes |
TCP |
License Serve |
License Server Agent Service |
|
59201 |
Yes |
TCP (HTTPS) |
License Server |
License Server Agent Service |
OMI Web Client
|
Port |
Can be configured |
Protocol |
Subsystem |
Purpose |
|---|---|---|---|---|
|
80 808 |
No |
TCP (HTTP) |
VCP |
vcp.services.onprem. vcp.services.onprem. |
|
443 80 |
No |
TCP (HTTPS) |
VCP |
vcp.services.onprem. |
Operations Control Logger
|
Port |
Can be configured |
Protocol |
Subsystem |
Purpose |
|---|---|---|---|---|
|
135 |
No |
TCP |
RPC |
Used for dynamic port mapping |
Platform Common Services (PCS)
|
Port |
Can be configured |
Protocol |
Subsystem |
Purpose |
|---|---|---|---|---|
|
80 |
No |
TCP (HTTP) |
PCS |
PCS.ServiceManager.exe |
|
443 |
Yes |
TCP (HTTPS) |
PCS |
PCS.Agent.exe(Discovery) PCS.IdentityManager.Host.exe |
|
808 |
Yes |
TCP |
PCS |
WCF shared port |
|
1900 |
No |
UDP (SSDP) |
PCS |
PCS.IdentityManager.Host.exe SSDP |
|
7084 7085 |
No No |
TCP |
PCS |
System authentication during node registration |
SQL Server
|
Port |
Can be configured |
Protocol |
Subsystem |
Purpose |
|---|---|---|---|---|
|
1433 |
Yes |
TCP |
SQL Server |
SQL Server |
|
1434 |
No |
UDP |
SQL Server |
SQL Server browser |
System Monitor
|
Port |
Can be configured |
Protocol |
Subsystem |
Purpose |
|---|---|---|---|---|
|
25 |
Yes |
TCP (SMTP) |
System Monitor |
SMTP Server |
|
80 |
Yes |
TCP (HTTPS) |
System Monitor |
Sentinel Console Service |
|
443 |
Yes |
TCP (HTTPS) |
System Monitor |
Secure Sentinel Console Service |
|
587 |
Yes |
TCP (SMTP) |
System Monitor |
Secure SMTP Server |