Configure batch events

  • Last UpdatedJan 14, 2025
  • 2 minute read

To generate hierarchical batch events using PI EFGen and the PI Event Frames Configuration Utility, configure three levels: Procedure, Unit Procedure, and Operation, as shown in the following figure:

Hiearchical batch example

Configuring procedure-level batch events

Configure the settings for this event type as follows:

Field

Setting

Configuration Name

RE100 Batch Procedure

Event Frame Template

EFSimProcedure

Active Point Name

RE100.Active

Active Point Behavior

Pulse

Event Frame Name

Choose Use this PIPoint value and enter TIME.YEARMONTHDAYTIME

In the Attribute Names table, configure the following attributes:

Attribute Name

Configuration

Value

Product

PIPoint

RE100.Product

Recipe

PIPoint

RE100.Recipe

Select the Other Settings tab. Omit the Primary Reference Element. In the Default Settings section, configure the following settings:

  • Recovery Time: 1 day

  • Evaluation Delay: 10 seconds.

To save the configuration, select Save Settings.

Configuring unit procedure-level batch events

Configure the settings for this event type as follows:

Field

Setting

Configuration Name

RE100 Unit Procedure (add as child of RE100 Batch Procedure)

Event Frame Template

EFSimUnitProcedure

Active Point Name

RE100.Active

Active Point Behavior

Pulse

Event Frame Name

Choose Use this PIPoint value and enter TIME.YEARMONTHDAYTIME

In the Attribute Names table, configure the following attributes:

Attribute Name

Configuration

Value

BatchID

PIPoint

TIME.YEARMONTHDAYTIME

Procedure

PIPoint

RE100.Procedure

Product

PIPoint

RE100.Product

Select the Other Settings tab and add RE100 as the primary reference element. In the Default Settings section, check Enable and configure an evaluation delay of 10 seconds. To save the configuration, select Save Settings.

Configuring operation-level batch events

Configure the settings for this event type as follows:

Field

Setting

Configuration Name

RE100 Operation (add as child of RE100 Unit Procedure)

Event Frame Template

EFSimOperation

Active Point Name

RE100.Phase

Active Point Behavior

Step

Event Frame Name

Choose ActivePoint value

No attribute configuration is required.

Select the Other Settings tab. Omit the primary reference element. In the Default Settings section, check Enable and configure an evaluation delay of 10 seconds. To save the configuration, select Save Settings.