Configuring State-Based Alarming on an Area Object
- Last UpdatedMay 19, 2022
- 1 minute read
State-based alarm modes apply to String attributes, with writeability set to Writeable_USC (these cannot be changed). To use state-based alarming for one or more areas, you must configure the PlantState attribute for each area that will use plant state-based alarming.

Configure plant state alarming
-
Open the area object and click the Attributes page.
-
Select the PlantState attribute.
-
Enable the I/O feature and select Read, Read/Write, or Write.
-
Enable the History feature and configure it.
-
Select the PlantStateAlarmMode.
-
Repeat steps 3 and 4 to configure the I/O and History features.