Communications Tab
- Last UpdatedJul 01, 2022
- 3 minute read

SuiteLink Mixed Mode Setting
Prior to System Platform 2023, enabling the System Management Server, either by connecting to an existing server or by setting this machine as the System Management Server resulted in the following behavior for SuiteLink connections:
-
The system first attempted to make a secure connection between a SuiteLink client and the SuiteLink server.
-
If a secure connection could not be established, an unsecured SuiteLink connection was made. Users were not notified if the SuiteLink connection was not secure.
As of System Platform 2023, the System Platform Configurator includes an option to force all communications to be encrypted for SuiteLink connections.
-
Mixed mode enabled: This is the default setting if you are upgrading a node from a prior release. With the checkbox set to true (checked), the behavior described above is used, in which unsecured connections are allowed. This mimics legacy System Platform behavior, prior to the System Platform 2023 release. This setting is NOT RECOMMENDED except for the use cases listed below.
-
Mixed mode disabled: This is the default setting for new installations. With the checkbox set to false (unchecked), client connections to the SuiteLink server are only successful if the connection is secured, that is both nodes must configured to use the System Management Server. This option ensures that the connection between the SuiteLink Server and SuiteLink clients is always secure (encrypted). If a secure connection is not available, the connection will not be allowed. A secure connection between client and server is only possible if both are configured to use the System Management Server.
Mixed Mode Use Cases
Mixed mode is recommended for use under the following conditions:
-
While upgrading an existing System Platform installation (performing a node-by-node upgrade). Reset the mode to disable mixed mode after the upgrade is complete.
-
To support legacy applications that do not use encrypted SuiteLink communications.
Note: Whenever the SuiteLink communication mode is changed, a system restart is required before the new mode will take effect.
NMX User Access Setting
The AVEVA Network Message Exchange (NMX) is an application communication protocol that leverages a DCOM-based transport mechanism for communication between nodes. For new installations, the default setting is to disable access for all users to NMX communications. If you are upgrading an existing System Platform installation, access for all users is enabled by default. Reset the mode to restrict access after you complete the node-by-node upgrade.
-
Grant access to NMX for all users: This is the default setting if you are upgrading a node from a prior release. With the checkbox to true (checked), NMX communication is enabled for all users. Allowing access for all users is NOT RECOMMENDED except for the use cases listed below.
-
Restrict access to NMX: This is the default setting for new installations. To restrict access to only users who are members of a well-known OS User Group, leave the setting as false (unchecked). This is the recommended setting.
Access to NMX for All Users Use Cases
Access for all users is recommended for use under the following conditions:
-
While upgrading an existing System Platform installation (performing a node-by-node upgrade). Reset the mode to disable access for all users after the upgrade is complete.
-
To support legacy applications that require access for all users.
Note: Whenever the NMX mode is changed, a system restart is required before the new mode will take effect.