About the AggregatedAlarmStatesIncluded Attribute
- Last UpdatedApr 06, 2022
- 1 minute read
AggregatedAlarmStatesIncluded is a four-element array that controls whether shelved, hidden, silenced, and/or disabled alarms are included in the values of the AlarmCntsBySeverity attribute. It is a galaxy-wide attribute. It is the same for all engines, areas, and objects.
The elements of AggregatedAlarmStatesIncluded are:
|
Element |
Alarm condition |
Default |
|
1 |
Shelved |
True |
|
2 |
Silenced |
True |
|
3 |
Disabled |
False |
|
4 |
Hidden |
False |
You can change the AggregatedAlarmStatesIncluded settings using the IDE. Follow the procedure below.
For more information about AlarmCntsBySeverity, see About the AlarmCntsBySeverity Attribute.
To configure the alarm states included in AlarmCntsBySeverity:
-
From the IDE main menu, select Galaxy, then select Configure, Galaxy, Alarms. This opens the Configure alarms and events dialog.
-
In the Aggregated alarms states included section at the bottom of the dialog, select the checkboxes for the alarm states to include in the AlarmCntsBySeverity totals and clear the checkboxes for those not to include.