Please ensure Javascript is enabled for purposes of website accessibility
Powered by Zoomin Software. For more details please contactZoomin

Analytics and Notifications for PI System Explorer (PI Server 2018)

Steam_VPX

  • Last UpdatedJan 11, 2023
  • 1 minute read

Calculate the steam specific volume as a function of pressure (P in kPa) and quality (vapor fraction). Use for only wet steam. By default, input arguments and returned values are in SI units. You can change the units of measure, for example, by using the Convert function.

Syntax

Steam_VPX(P, X)

Arguments

  • P

    Pressure of the steam. P can range from 0.611212678 to 22064 kPa.

  • X

    Steam quality (vapor fraction). X can range from 0.0 to 1.0.

Returns

Computed steam specific volume in cm3/g

Example

  • Steam_VPX(15000, 0.7)

    [Returns 7.7352cm3/g]