In the case of an OPC Client, the following error code support is used:

Return Code

Description

S_OK

The corresponding item handle was valid. The write will be attempted and the results will be returned on OnWriteComplete.

E_FAIL

The function was unsuccessful.

OPC_E_BADRIGHTS

The item is not writeable.

OPC_E_INVALIDHANDLE

The passed item handle was invalid.

OPC_E_UNKNOWNITEMID

The item is no longer available in the data source’s address space.

E_xxx

S_xxx

Vendor specific errors may also be returned. Descriptive information for such errors can be obtained from GetErrorString.

A failed write to an ArchestrA data source is handled as follows:

  • If ArchestrA responds with Nak, FSGateway sends an E_FAIL error code to the OPC Client.

  • If FSGateway cannot successfully convert the requested OPC data, this maps to a new vendor specific error for OPC indicating "Conversion Error" (OPC_E_BADTYPE).

  • If the item handle is unknown to FSGateway or ArchestrA, the OPC_E_INVALIDHANDLE error code is sent.

  • If the item name is not valid in FSGateway or ArchestrA, the OPC_E_UNKNOWNITEMID error code is sent.