Notes regarding hot backup pairs

  • Last UpdatedJul 19, 2024
  • 1 minute read
  • You can use a hot backup only for InTouch 7.11 and later clients.

  • If the Distributed Alarm Display object queries a hot backup pair and then queries the primary provider again separately, the Distributed Alarm Display object shows duplicate records.

  • Do not configure a provider as a primary or secondary of more than one hot backup pair.

  • If a record at the primary provider is acknowledged and the secondary provider (which was down when the acknowledgment took place) starts up at a later time, the time stamp of the acknowledged record is identical with the record in the primary provider.

  • The alarm consumer querying a hot backup pair shows the individual node name as the provider.

  • You can choose any combination of design-time and run-time alarm record fields for mapping. However, be sure that the mappings do not result in multiple references.

  • When mapping the Value and Limit key fields, the values are rounded off to the fourth decimal place and then mapped.

  • An alarm record that does not have the specific combination of design-time and run-time mapping uses the default runtime mapping.