Message

Meaning

07-Dec-07 16:57:34
PIDNP3 1> Starting PI DNP3 Interface Version 3.0.1.0
Build Date: 07-Dec-2007 16:55:27

This message informs the user that the interface is starting and lists the version number of the interface.

Message
07-Dec-07 16:57:34
PIDNP3 1> INFO> The interface is configured using the following startup parameters:
Interface instance (/Id): 1
Interface debug level (/DNPDbg):
0x00000001
Write I/O Timeout (/IOTimeOut): No
XML Configuration file (/XML):

D:\PI\interfaces\DNP3\pidnp3.xml
Connection retry rate (/Retry): 10 seconds
Thread pool size (/IOPool): 5
DNP3 Event class (/Event): Scanclass 1
Log RTU configuration (/NoLogRTUParams): Yes
Maximum log file size (/RTULogSize): 100KB
Device status log (/NoDevStatLog): Yes,

d:\PI\interfaces\DNP3\devstat\ pidnp3_devstat_1.csv

This message informs the user of the parameters being used for interface startup.

07-Dec-07 16:57:34
PIDNP3 1> INFO> There are 2 RTU(s) assigned to the interface.

Capacitor #123456789(4), Capacitor #987654321(5)

This message informs the user of the RTU Name (DNP3 Address) assigned to the interface.

07-Dec-07 16:57:34
PIDNP3 1> Parameters for RTU Name: Capacitor #23495246, Address: 4

RTU Master Address: 3

Communication will be via 192.168.45.30:20000

Event type data timestamped with UnAdjusted RTU time.

RTU time will be synchronized with PI every 24 hours.

RTU time is Local Standard Time (LST).

Integrity Scans every 2 minute(s).

Integrity scans immediately after a communications failure.

Attempt to clear the IIN “Restart” bit if set.

This message informs the user of the parameters defined in the xml configuration file that are being used for the RTU.

07-Dec-07 16:57:35
PIDNP3 1> RTU Name: Capacitor #23495246, Address: 4

RTU reset on communication medium >

192.168.45.30:20000.

There are 37 PI-Point(s) assigned to this RTU.

This message informs the user that the interface is connected to the RTU and displays the number of points configured for the RTU.