Analog control block (object 41) point
- Last UpdatedNov 18, 2022
- 1 minute read
- PI System
- PI Interface for DNP3 3.3.1.38
- Interfaces
The Userint2 attribute is necessary when writing output values to the Analog Control Block (Object 41). The use of these objects is specified by setting the Location5 attribute to a value 41. The following table lists the value that the Userint2 attribute must be set to when requesting a specific DNP3 function.
|
Function |
Userint2 Value |
|---|---|
|
Select and Operate |
0 |
|
Direct Operate |
1 |
|
Direct Operate, No Ack |
2 |