Apps, Widgets, and Controls

Save runtime modifications to queries and filters

  • Last UpdatedJul 19, 2024
  • 1 minute read

You can save modifications made to queries and filters at runtime. There is an option to save user queries and filters in the Run-Time Behavior tab of the Edit Animations dialog box. It is selected by default, as shown below:

SaveUserQueries_checkbox

When this option is selected, modifications made to queries or filters at runtime are saved on a per user and alarm control instance to a XML file. For example, a saved query will save as UserQueryFilter_001.xml.

Modifications are saved in the following default directory:

C:\Users\<OS Login Name>\AppData\Local\Wonderware

The map between the Alarm Control instance and the above XML file is saved in a map file, "InstancesMap.dat".

Modified queries and filters will be available upon closing and restarting the alarm control window or WindowViewer.

If you uncheck the Save User Queries and Filters option, updates made to queries and filters during run-time will not be saved.

Note: When the Save User Queries and Filter option is checked, the Overwrite Design Time Queries and Filters option is enabled and checked by default. When checked, this option resolves naming conflicts between design-time queries and filters and runtime queries and filters loaded from the XML file. Naming conflicts will be resolved by overwriting the design time queries and filters.