Apps, Widgets, and Controls

Hide alarms

  • Last UpdatedJul 19, 2024
  • 2 minute read

The "hiding" and "unhiding" of alarm records is known in the corresponding InTouch alarm controls as "suppressing" and "unsuppressing".

When the Alarm Control is hiding alarms, it ignores certain alarms. If an alarm matches the exclusion criteria, it is not visible.

The actual alarm generation is completely unaffected by hiding. Alarm records are still logged into the alarm history.

You can hide:

  • All alarms, including alarms not visible due to the limited space of the Alarm Control

  • All visible alarms

  • One or more selected alarms

  • All alarms with the same provider names and group names of one or more selected alarms

  • All alarms with the same provider names, group names, and within the priority ranges of one or more selected alarms

  • All alarms with the same provider names, group names, and tag names within the priority ranges of one or more selected alarms

You can also view which alarms are hidden and unhide them.

To hide all alarms

  • Right-click the Alarm Control grid, point to Hide Others, and click Hide All

To hide all visible alarms

  • Right-click the Alarm Control grid, point to Hide Others, and click Hide Visible

To hide selected alarms

  1. Select one or more alarms in alarm state.

  2. Right-click the Alarm Control grid and click Hide Selected.

To hide alarms with common parameters

  1. Select one or more alarms.

  2. Right-click the Alarm Control grid, point to Hide Others, and click one of the following:

    • Hide Selected Groups to hide alarms with the same provider names and group names of one or more selected alarms

    • Hide Selected Tags to hide alarms with the same provider names, group names, and tag names within the priority ranges of one or more selected alarms

    • Hide Selected Priorities to hide alarms with the same provider names, group names, and within the priority ranges of one or more selected alarms

    To unhide alarms

    1. Right-click the Alarm Control grid and click Hidden. The Hidden Alarms dialog box appears.

    2. Select the alarms you want to unhide and click Unhide.

    3. Click Close.