AVEVA™ System Platform

InTouch HMI Issues

  • Last UpdatedJul 24, 2022
  • 1 minute read

The following known issues are in addition to those documented in the InTouch HMI Readme.

Issue Number

Description

-

On a fresh installation of System Platform 2023, you may notice the following issues related to Secure Suitelink Connection:

  • The Suitelink client does not connect to the WindowViewer

  • The Web Client does not bind to InTouch tag.

  • When WindowViewer is launched, the system displays the SuiteLink error message in the Logger.

Workaround:

To ensure connectivity between the Suitelink client and the WindowViewer:

  • Enable System Management Server in the Configurator.

  • Configure Secure Suitelink connection (V3).

  • Enable Unsecure Suitelink connection (V2) fall back.

For more information, see Configuring a Secure Suitelink Communication in the AVEVA InTouch HMI Help.

1928318

When the Supertag instances are created by importing from a .CSV file, the imported Supertags are not displayed in the Supertags pane of the WindowMaker.

Workaround: The Supertag instances created by importing from a .CSV file can be viewed in the tag dictionary.

IMS-1488851

Post-upgrade from InTouch HMI 2017 U3 SP1 to InTouch HMI 2020 R2 SP1, the following warning message is logged in the LogViewer:

“Unable to start the aaServiceHost Could not load file or assembly 'PCS.Client.Discovery, Version=1.3.1.0, Culture=neutral, PublicKeyToken=23106a86e706d0ae' or one of its dependencies. The system cannot find the file specified.”

This has no functional impact. However, restarting the system will resolve the message.