The following table lists ports used by System Platform products.

Note: Firewall settings for all destination ports must allow INBOUND connections.

Product

Process Name

Port

Add'l Port

Config-
urable

Description

Protocol

Application Server

aaBootstrap.exe

30000

Yes

Local redundancy primary port (WinPlatform)

TCP and UDP

30001

Yes

Local redundancy message port (WinPlatform)

TCP

49152 to 65535

No

DCOM port range

TCPV6

135

No

DCOM and RPC

TCP

139

No

DCOM and Netbios (Bootstrap)

TCP

445

No

DCOM and Netbios (Bootstrap)

TCP

aaGlobalDataCache
MonitorSvr.exe

49152 to 65535

No

DCOM port range

TCPV6

aaGR.exe

49152 to 65535

No

DCOM port range

TCPV6

8090

Yes

Configurable through registry: HKLM\SOFTWARE\ArchestrA\Framework\Remoting with key "defaultPort" and Value as <port number> string

TCP

49152 to 65535

No

DCOM port range

TCP and TCPV6

aaEngine.exe

32568

Yes

"TCP Port" (WinPlatform Engine advanced settings)

TCP

aaObjectViewer.exe

49152 to 65535

No

DCOM port range

TCPV6

aaPIM.exe

49152 to 65535

No

DCOM port range

TCPV6

aaPlatformInfoSvr.
exe

49152 to 65535

No

DCOM port range

TCPV6

aaUserValidator.exe

49152 to 65535

No

DCOM port range

TCPV6

NmxSvc.exe

5026

Yes

Message Exchange port number (WinPlatform)

TCP

Multi Galaxy

808

No

ASBMxDataProvider Service

TCP

808

No

Galaxy Pairing

TCP

808

No

ASBGRBrowsing Service

TCP

808

No

ASBAuthentication Service

TCP

PCS/ Historian

3575

Yes

Event Service

TCP

PCS/ Historian Service (PCS InProc Hosting)

3586

Yes

EventHistorian Service

TCP

PCS

PCS.IdentityManager.
Host.exe SSDP

1900

Yes

UDP

Asb.Discovery.exe, PCS.IdentityManager
.Host.exe

443

Yes

HTTPS

7084

Yes

System authentication (only available during node registration)

TCP

7085

Yes

System authentication (only available during node pairing)

TCP

Asb.Watchdog.exe, Asb.ServiceManager
.exe, PCS.IdentityManager
.Host.exe

80

Yes

HTTP

any

Yes

OPC UA Server

TCP

Historian

135

MDAS -Used by client nodes prior to ASP 2012 R2

TCP and UDP

136

IDAS and Remote IDAS prior to Historian 2017

TCP and UDP

137

IDAS and Remote IDAS prior to Historian 2017

TCP and UDP

138

IDAS and Remote IDAS prior to Historian 2017

TCP and UDP

139

IDAS and Remote IDAS prior to Historian 2017

TCP and UDP

445

File and printer sharing

TCP

445

Remote IDAS prior to Historian 2017

TCP and UDP

1433

Yes

SQL Server - Used by Historian Client. Historian and Historian Client 2017 and later support non-default ports.

TCP

1434

SQL Server Browser

UDP

aahClientAccess
Point.exe

32568

Yes

Historian, Remote IDAS 2017 and later, and Redundant AppServer node./HCAL/HCAP

TCP

Historian Insight, OData

aahGateway.exe

32569

Yes

Configured in Historian System Parameter “GatewayTcpPort.”Configurable in Historian 2017 and later

TCP

Licensing

License Manager

80

Yes

License Manager

License Server Core Service

55555

Yes

License Server Core Service

License Agent

59200

Yes

License Agent

License Manager to Activation server outbound

443

Yes

License Manager to Activation server outbound

OI Server

SI Direct

102

OI Server

MBTCP

502

OI Server

ABTCP

2221

OI Server

2222

OI Server

2223

OI Server

S/L OI Servers

5413

OI Server

DBServer

5481

Yes

ATS

TCP

ABCIP

44818

OI Server

TCP

GESRTP OI Server

18245

OI Server

OI Gateway

OI Gateway

1883, 8883

Yes

OI Gateway MQTT connectivity

InTouch Access Anywhere

AccessServer64.
exe

8080

Server

TCP

57733

Server

TCP

57734

Server

TCP

57735

Server

TCP

3399

Server

TCP

EricomSecure
Gateway.exe

443

Secure Gateway

TCP

57111

Secure Gateway

UDP

Intouch Web Client

InTouchWeb.
ContentHost.exe

60152

60153

InTouch Web Client

TCP

InTouchWeb.Host.
exe

60236

60237 60238 60311 60312

InTouch Web Client

TCP

InTouchWeb.Server.
exe

60161

60162

InTouch Web Client

TCP

Intouch

InTouchDataService.
exe, used for InTouchiData

58398

60118

InTouchiData

TCP

Suitelink

5413

TCP

49152 to 65000

TCP

Alarm Logger

aaLogger.exe

1041

Alarm Logger

TCP

5004

Alarm Logger

TCP

Alg.exe

1087

Alarm Logger

TCP

Alarm Manager

Alarmmgr.exe

51218

TCP

System Monitor

80

Yes

HTTP

443

Yes

HTTPS

25

Yes

SMTP

587

Yes

SMTPS