Configure graphics
- Last UpdatedOct 01, 2024
- 2 minute read
Industrial Graphics contain custom properties that extend the standard properties of a symbol. In this sample application, you must assign tags to custom properties to show the current value of a tag or set the states when the equipment represented by a symbol is active or inactive.
Most Situational Awareness Library symbols are also Symbol Wizards. In addition to custom properties, Symbol Wizards contain Wizard Options to configure their appearance and functionality.
This procedure explains how to assign values to the custom properties and Wizard Options listed in the following tables.
Graphic Custom Properties
|
Graphic |
Custom Property |
Assigned Values |
|---|---|---|
|
Liquid Rocker Switch |
Value |
Valve_Liquid |
|
Concentrate Rocker Switch |
Value |
Valve_Concentrate |
|
Outlet Rocker Switch |
Value |
Valve_Outlet |
|
Liquid Valve |
EquipmentStateActive |
Valve_Liquid |
|
Concentrate Valve |
EquipmentStateActive |
Valve_Concentrate |
|
Outlet Valve |
EquipmentStateActive |
Valve_Outlet |
|
Mixing Tank |
LabelVisible |
True |
|
Tank Agitator |
EquipmentStateActive |
True |
|
PV |
Agitator_RPM |
|
|
PVRangeFullScaleMax |
3000 |
|
|
PVRangeFullScaleMin |
0 |
|
|
Tank Volume Meter |
PV |
Tank_Level |
|
PVRangeFullScaleMax |
1500 |
|
|
PVRangeFullScaleMin |
0 |
|
|
Tank Volume Trend |
Pen |
Tank_Level |
|
Pen_RangeFullScaleMax |
1500 |
|
|
Pen_RangeFullScaleMin |
0 |
|
|
Alarm Client |
None |
N/A |
Symbol Wizards
|
Symbol Wizards |
Wizard Options |
Assigned Values |
|---|---|---|
|
Liquid Rocker Switch |
None-Industrial Graphic |
N/A |
|
Concentrate Rocker Switch |
None-Industrial Graphic |
N/A |
|
Outlet Rocker Switch |
None-Industrial Graphic |
N/A |
|
Liquid Valve |
ActuatorType |
Digital |
|
Concentrate Valve |
ActuatorType |
Digital |
|
Outlet Valve |
ActuatorType |
Digital |
|
Liquid Fertilizer Tank |
QualityStatusIndicator |
False |
|
Tank Agitator |
PVNumericDisplay |
True |
|
EngUnits |
True |
|
|
EngUnitsType |
StaticText |
|
|
QualityStatusIndicator |
False |
|
|
Tank Volume Meter |
Type |
Level |
|
Tank Volume Trend |
SymbolMode |
Advanced |
|
YAxisRangeType |
ClipOutOf RangeValues |
|
|
PlotType |
Line |
|
|
Label |
True |
|
|
LabelType |
StaticText |
|
|
GridVerticalTimePeriod Scale |
True |
|
|
GridVerticalTimePeriodScaleUnits |
True |
|
|
TimePeriod |
True |
|
|
Alarm Client |
None |
N/A |
To configure custom properties and Wizard Options
-
Double-click on the Liquid rocker switch to show the Edit Symbol Properties dialog box.

-
Select Value from the Name field.
-
Click the Browse button at the right of the Default Value field to show the Select Tag dialog box.

-
Select the Valve_Liquid tag and click OK.
The current value of the Valve_Liquid tag is associated to the Liquid rocker switch’s Value custom property.
-
Repeat steps 1-4 for the other two rocker switch symbols and assign the tag shown in the Symbol Custom Properties table to each symbol’s Value custom property.
-
Double-click on the Liquid valve to show the Edit Symbol Properties dialog box.
-
Using steps 1-4, assign the Valve_Liquid tag to the symbol’s EquipStateActive custom property.
-
Click the Wizard Options tab.
-
Select ActuatorType from the Name field.
-
Set the Value field to Digital and click OK.
-
Repeat steps 1-10 and assign values to the custom properties and Wizard Options of the remaining symbols of the Liquid Fertilizer application.