Location5

  • Last UpdatedNov 16, 2022
  • 1 minute read

The Location5 attribute enables and disables exception reporting and determines how to handle multiple events at the same time stamp on a point-by-point basis. The table below lists the recognized settings.

Location5 settings

Setting

Description

-1

Enables exception reporting specifically to ascending time-series data collected before the snapshot

0

Enables exception reporting

1

Disables exception reporting, and for multiple values collected for a single time stamp, uses the mode replace.

2

Disables exception reporting, and for multiple values collected for a single time stamp, uses the mode append.

Note: To suppress exception reporting for all PI points, enable the startup parameter /LB or /LBS. If either of the two start-up parameters is specified, Location5 attribute is not reflected. For more information, see the topic Command-line parameters for the PI UFL interface.