Please ensure Javascript is enabled for purposes of website accessibility
Powered by Zoomin Software. For more details please contactZoomin

PI Interface for OPC DA

Processing type attribute (location3)

  • Last UpdatedNov 15, 2022
  • 1 minute read

The location3 attribute specifies whether this PI point is a polled, advise, event, or output point. For definitions of these input points, refer to Input points.

Location3

Description

0

Polled or event

1

Advise

2

Output

3

Polled watchdog used with server-level failover

4

Advise watchdog used with server-level failover

For an advise point, PI Interface for OPC DA registers for updates with the OPC server, and the OPC server sends new values to the interface. The update rate from the server does not exceed the update rate for the group.