Please ensure Javascript is enabled for purposes of website accessibility
Powered by Zoomin Software. For more details please contactZoomin

PI System Management Tools

Associated points

  • Last UpdatedFeb 20, 2025
  • 2 minute read

Associated points generally provide limit and reference values used in SQC calculations.

SQC Alarm Editor in PI System Management Tools, showing fields for configuring associated tags, control limits, reset points, and optional tags.

Perform the following steps to specify the points required for SQC calculations:

  • Use the provided fields to enter or change the tag names of associated points, if necessary. You can also click the ellipsis button to search for tags on the Data Archive server. If you are creating a new alarm using Automatic Point Generation, the tag names are already created for you.

  • Use the provided fields next to each tag name to enter initial limit values for each point.

If desired, you can add and specify optional points:

  • Check the box next to each optional point type you want to add, then enter a tag name or click to search for a tag on the server.

    The following default points must be defined for a real-time SQC alarm:

    Tag Alias

    Description

    Source Tag

    The point on which alarm calculations are performed

    Reset Tag

    The point whose value sets the execution status of the pattern test evaluation

    UCL Tag

    The point whose value is the upper control limit for the chart

    CL Tag

    The point whose value is the center line for the chart

    LCL Tag

    The point whose value is the lower control limit for the chart

    The following optional points can be associated with a real-time SQC alarm:

    Tag Alias

    Description

    Test Status Tag

    The point whose value corresponds to all pattern tests currently in alarm condition

    USL Tag

    The point whose value is the upper specification limit for the chart

    LSL Tag

    The point whose value is the lower specification limit for the chart

    Comment Tag

    The point used to store comments associated with the SQC alarm

Related Links