Please ensure Javascript is enabled for purposes of website accessibility
Powered by Zoomin Software. For more details please contactZoomin

Plant SCADA

[Alarm]DBLogAlmSummary

  • Last UpdatedMar 19, 2025
  • 1 minute read

Use this parameter to define logging for alarm summary operations on the alarm server database.

Note: The value for this parameter should not be changed from the default unless advised by Technical Support.

This parameter can be applied to a specific cluster or alarm server process. For more information, see Configure Alarm Parameters for a Specific Cluster or Process.

Allowable Values:

An integer representing one of the following logging masks, or the sum total of integers representing multiple logging masks:

Logging Mask

Description

Integer

ALSERR

Alarm summary errors

1

ALSDAT

Alarm summary file operations

2

ALSSBY

Alarm summary standby transfer

4

ALSREC

Alarm summary record operations

8

ALSWRT

Alarm summary new records

16

ALSENUM

Alarm summary enumerate files

32

ALSDET

Alarm summary detailed file operations

64

Default Value:

3 (ALSERR + ALSDAT logging)

Example

To enable logging for alarm summary errors (set using "1"), alarm summary file operations (set using "2") and alarm summary record operations (set using "8"), you would add the integers for each and set the parameter to the following:

[Alarm]DBLogAlmSummary=11

See Also

[Alarm]DBLogJournal

[Alarm]DBLogKernel

[Alarm]DBLogServerCore

Alarm Parameters

In This Topic
Related Links