[Alarm]DBLogKernel

  • Last UpdatedSep 13, 2024
  • 1 minute read

Use this parameter to turn on logging for the alarm server database.

Note: The value for this parameter should not be changed from the default unless advised by Technical Support.

This parameter can be applied to a specific cluster or alarm server process. For more information, see Configure Alarm Parameters for a Specific Cluster or Process.

Allowable Values:

An integer representing one of the following logging masks, or the sum total of integers representing multiple logging masks:

Logging mask

Description

Integer

ERR

Database errors

1

OBJ

Database kernel

2

QP

Query processor

4

RDR

Alarm redirection

8

ARC

Historic archive

16

BKP

Backup

32

CRC

Configuration Change CRC

64

IDX

Database index searches

128

LCK

Database locks

256

SYS

System calls

512

ALMSTA

Alarm state changes

1024

AEFIL

Alarm and event filtering

2048

CFGTRN

Config transactions

4096

META

Metadata

8192

CFGTIM

Config timings

16384

POP

POP3 / IMAP incoming mail

32768

GSI

Geospatial Index

65536

EXTAUTH

External authentication

131072

EXTGRPS

External group memberships

262144

BKP_V

Backup (verbose)

524288

Default Value:

143935 (ERR + OBJ + QP + RDR + ARC + BKP + SYS + CFGTRN + META + EXTAUTH logging)

See Also

[Alarm]DBLogAlmSummary

[Alarm]DBLogJournal

[Alarm]DBLogServerCore

Alarm Parameters