Plant SCADA

HistorianConnector​.Citect​.Properties​.Settings

HistorianConnector​.Citect​.Properties​.Settings

  • Last UpdatedMar 26, 2025
  • 3 minute read

The following settings are found in the HistorianConnector.Citect.Properties.Settings section.

MaxBackfillRange

The maximum backfill range, as a number of days, for AVEVA Plant SCADA trend tags, alarms, and events. This setting only applies to the first startup of the AVEVA Historian Plant SCADA Connector, defining how far back from the current date the Connector will start requesting data. On subsequent startups, the Connector will resume requesting data from the point where it last stopped, ignoring the maximum backfill range.

The value is stored as a time range in the following format:

  • d.HH:mm:ss

where

  • d = The number of days

  • HH = The number of hours

  • mm = The number of minutes

  • ss = The number of seconds

Valid values include:

  • Minimum = 0 (0.00:00:00)

  • Default = 1 day (1.00:00:00)

    Note: This setting only applies to the first startup, so if you want to change the setting after you have already started up the Connector, you should stop the Connector, remove the SQLite database found in C:\ProgramData\Wonderware\Citect SCADA Connector\Data, change the MaxBackfillRange setting, and then restart the Connector. If the Connector sends duplicate Trend history to the Historian, the duplicate data is ignored.

MaxRecordsToRead

The maximum number of records to retrieve in a single request from the AVEVA Plant SCADA alarm server.

Valid values include:

  • Minimum = 1

  • Default = 20000

LateAlarmToleranceDays

The number of days tolerance to apply to "late" alarms (that is, where eventTime is less than receiptTime).

Valid values include:

  • Minimum = 0

  • Maximum = 31 days

  • Default = 1 day

FutureAlarmToleranceHours

The number of hours tolerance to apply to "future" alarms (that is,clock drift).

Valid values include:

  • Minimum = 0 hrs

  • Maximum = 24 hours

  • Default = 1 hr

PriorityRangeToSeverityCritical

The range of priority values in AVEVA Plant SCADA that correspond to a critical severity (severity = 1) in AVEVA Historian.

The default range is priority values 1-250.

PriorityRangeToSeverityHigh

The range of priority values in AVEVA Plant SCADA that correspond to a high severity (severity = 2) in AVEVA Historian.

The default range is priority values 251-500.

PriorityRangeToSeverityMedium

The range of priority values in AVEVA Plant SCADA that correspond to a medium severity (severity = 3) in AVEVA Historian.

The default range is priority values 501-750.

PriorityRangeToSeverityLow

The range of priority values in AVEVA Plant SCADA that correspond to a low severity (severity = 4) in AVEVA Historian.

The default range is priority values 751-999.

Note: AVEVA Plant SCADA supports priority levels from 1 through 255, but in some situations you can set the priority to a value of 0. The AVEVA Historian Plant SCADA Connector maps priority value 0 in AVEVA Plant SCADA to severity level 4 (low) in AVEVA Historian.

IsClusterPartOfModel

Enables or disables cluster options. The default value is True.

Valid values include:

  • True - Cluster options are enabled.

  • False - Cluster options are disabled.

This affects the HierarchicalName and Location properties for item and equipment entities.

Equipment Defined?

Item Defined?

IsCluster PartOfModel

Hierarchical Name

Location

No

No

True or False

.

/

Yes

Yes

True

<Equipment Name End Part>.<Item Name>

/<Cluster>/<Equipment Name Parent Part>/<Equipment Name End Part>

Yes

Yes

False

<Equipment Name End Part>.<Item Name>

/<Equipment Name Parent Part>/<Equipment Name End Part>

Yes

No

True

<Equipment Name End Part>.<Tag Name>

/<Cluster>/<Equipment Name Parent Part>/<Equipment Name End Part>

Yes

No

False

<Equipment Name End Part>.<Tag Name>

/<Equipment Name Parent Part>/<Equipment Name End Part>

Example 1

Given a trend tag Bottler_CapConveyor_PM800\MMXU1\TotPF with the equipment name Plant.Bottler.CapConveyor.PM800, the item defined as PowerFactorTotal, and with cluster Cluster1, the Hierarchical Name and Location are represented according to the following table:

Equipment Defined?

Item Defined?

IsCluster PartOfModel

Hierarchical Name

Location

No

No

True or False

.

/

Yes

Yes

True

PM800.PowerFactorTotal

/Cluster1/Plant/Bottler/CapConveyor/PM800

Yes

Yes

False

PM800.PowerFactorTotal

/Plant/Bottler/CapConveyor/PM800

Yes

No

True

PM800.Bottler_CapConveyor_PM800\MMXU1\TotPF

/Cluster1/Plant/Bottler/CapConveyor/PM800

Yes

No

False

PM800.Bottler_CapConveyor_PM800\MMXU1\TotPF

/Plant/Bottler/CapConveyor/PM800

Example 2

If the equipment name is defined, but the equipment is at the root level of the hierarchy, the Hierarchical Name and Location are represented according to the following table. For example, if the equipment name is defined as Pump1, with cluster Cluster1:

IsCluster PartOfModel

Item Defined?

Hierarchical Name

Location

False

No

Pump1.<Tag Name>

/Pump1

False

Yes

Pump1.<Item Name>

/Pump1

True

No

Pump1.<Tag Name>

Cluster1/Pump1

True

Yes

Pump1.<Item Name>

Cluster1/Pump1