Configuring Device Redundancy
- Last UpdatedMay 18, 2018
- 2 minute read
The OI Server Manager provides the ability to assign redundant device for fail-over protection in the event of device failure. Two devices must be configured in the same OI Server having identical item syntax.
Primary and secondary devices will be setup in the REDUNDANT_DEVICE object in the SMC, along with a common item name (ping item) shared by each device to determine device status.
To setup up a REDUNDANT_DEVICE from the configuration branch
-
Set-up a primary device and hierarchy in the OI Server Manager in the SMC.
-
In the Device Items tab, create at least one device item that can be shared between the primary and secondary devices to determine device status.
-
Set up a secondary device on the same OI Server. Once again, create an identical device item within the secondary device so that device status can be determined.
-
Select and right-click on the Configuration node, and select Add REDUNDANT_DEVICE Object.
An object called New_REDUNDANT_DEVICE_000 is created. Rename the newly created object as appropriate.
-
In the New_REDUNDANT_DEVICE_000 Parameters configuration screen, specify the primary and secondary devices. Alternately, click the browse (...) button to view the Device Browser screen, that allows you to select the primary and secondary devices.
-
Specify the Ping Item which is a valid tag in both the primary and secondary controllers to determine the connection status for $SYS$Status.
The ping item can be a static item in the device such as a firmware version or processor type. If the ping item is invalid or does not exist in the controller, the failover operation may not work correctly as the value of $SYS$Status may continue to stay as FALSE in the standby device.
-
Click Save to save the hierarchy node configuration.
Note: Unsolicited message configuration is not supported from the device redundant hierarchy.