AVEVA™ Communication Drivers

Counter Section Items

  • Last UpdatedOct 23, 2017
  • 1 minute read

[m]C[n]:e[.f][/b]

m indicates the module to access. If not specified, it is assumed to be 0 (zero), which selects the Resource Manager. If specified, it must be 0 (zero) or the thumbwheel setting for a Logic Processor.

n represents the file number. If not specified, it is assumed to be 0 (zero). If specified, the file number must be 0 - 9999 decimal.

e specifies the element number (three words per element) within the Counter file. It must be 0 - 9999 decimal.

.f identifies one of the valid Counter fields. The valid fields for the Counter section are listed in the table. If .f is omitted, it is assumed to be the word containing the status bits.

b is optional and is normally not used. All of the fields of a Counter can be accessed by specifying the .f fields. However, it is possible to use /b to single out a bit in the .PRE or .ACC fields (which are words). For Counter files, the bit number must be 0 - 15 decimal.

Examples:

C5:0.ACC

1C9:3.OV

0C:1.PRE