AVEVA™ Communication Drivers

Control Section Items

  • Last UpdatedOct 23, 2017
  • 1 minute read

[m]R[n]:e[.f][/b]

m indicates the module to access. If not specified, it is assumed to be 0 (zero), which selects the Resource Manager. If specified, it must be 0 (zero) or the thumbwheel setting for a Logic Processor.

n represents the file number. If not specified, it is assumed to be 0 (zero). If specified, the file number must be 0 - 9999 decimal.

e specifies the element number (three words per element) within the Control file. It must be 0 - 9999 decimal.

.f identifies one of the valid Control fields. The valid fields for Control files are listed in the table. If .f is omitted, it is assumed to be the word containing the status bits.

b is optional and is normally not used. All of the fields of a Control file can be accessed by specifying the .f fields. If specified, it indicates the bit (0 - 15 decimal).

Examples:

1R:0.LEN

R9:3.EM

0R:1.POS