AVEVA™ Communication Drivers

Timer Section Items

  • Last UpdatedOct 23, 2017
  • 1 minute read

[m]T[n]:e[.f][/b]

m indicates the module to access. If not specified, it is assumed to be 0 (zero), which selects the Resource Manager. If specified, it must be 0 (zero) or the thumbwheel setting for a Logic Processor.

n represents the file number. If not specified, it is assumed to be 0 (zero). If specified, the file number must be 0 - 9999 decimal.

e specifies the element number (six words per element) within the Timer file. It must be 0 - 9999 decimal.

.f identifies one of the valid Timer fields. The valid fields for Timer files are listed in the table.

b is optional and is normally not used. Specifying the .f fields can access all of the fields of a timer. For Timer files, the bit number must be 0 - 31 decimal.

Examples:

T:0.ACC

1T9:3.DN

T:1.PRE