Please ensure Javascript is enabled for purposes of website accessibility
Powered by Zoomin Software. For more details please contactZoomin

Plant SCADA

Plant SCADA and Application Server components reference

Plant SCADA and Application Server components reference

  • Last UpdatedNov 03, 2026
  • 3 minute read

Use the following information to determine which Plant SCADA components are imported into Application Server by the Integration Assistant, and how they will be configured once the import process is complete. Each section aligns with an activity in Plant SCADA Studio.

Note: Any expressions that are detected in a Plant SCADA project will be converted to QuickScript when integrated into Application Server. However, there are some limitations. For more information, see Support for expressions in QuickScript.

Topology activity

Application Server does not require direct access to the physical hardware in a Plant SCADA system, so the information in the Topology activity is not imported by the Integration Assistant.

Plant SCADA component

Application Server

Notes

Computers

Not supported

Clusters

Not supported

Network Addresses

Not supported

Servers

Not supported

Profiles

Not supported

I/O Devices

Not supported

Boards

Not supported

Ports

Not supported

Modems

Not supported

Remapping

Not supported

System model activity

Plant SCADA component

Application Server

Notes

Equipment Type

Template

Each Equipment Type needs to contain valid Items with supported elements.

Items

Attribute

Each Item needs to have a unique name within an Equipment Type.

Expressions are not supported in Item names.

Elements

Attribute Feature

States

Not supported

Configuration parameters

Not supported

Linked Genies

Not supported

Instances

Object instances

If an Equipment Instance is not associated with a valid Equipment Type, it will be integrated into Application Server using a generated template.

Runtime parameters

Not supported

References

Not supported

Variables

Feature - I/O (read/write)

A variable tag will not be integrated into Application Server if its data type is defined as ULONG.

If an unrecognized data type is used, or the data type definition contains an expression, the variable tag will not be integrated.

Local variables

Not supported

Digital alarms

Feature - State alarm

Time stamped alarms

Not supported

Analog alarms

Feature - Limit alarm, ROC alarm, Deviation alarm

If an analog alarm has delays configured for any alarm limits (High High Delay, High Delay, Low Delay, Low Low Delay), make sure they are all set to the same delay period. Application Server will only support one delay period for alarm limits.

Advanced alarms

Feature - State alarm

The alarm will have an associated script on the parent object.

Note: Advanced alarms containing Cicode functions are not supported. See Support for expressions in QuickScript.

Multi-digital alarms

Feature - State alarm

Application Server does not support multi-digital alarms. However, multi-digital alarms with only two states configured (only 000 00A) can be converted to a digital alarm.

Time stamped digital alarms

Feature - State alarm

Time stamped analog alarms

Feature - Limit alarm, ROC alarm, Deviation alarm

If a time stamped analog alarm has delays configured for any alarm limits (High High Delay, High Delay, Low Delay, Low Low Delay), make sure they are all set to the same delay period. Application Server will only support one delay period for alarm limits.

Double point status alarms

Not supported

Trends

Feature - History

Trend triggers are not supported in Application Server.

Accumulators

Not supported

SPC

Not supported

Visualization activity

Plant SCADA graphics are not imported into Application Server.

Plant SCADA component

Application Server

Notes

Menu configuration

Not supported

Pages

Not supported

Symbols

Not supported

Content types

Not supported

Keyboard commands

Not supported

Reports

Not supported

Security activity

Plant SCADA's users and groups are not imported into Application Server.

Plant SCADA component

Application Server

Notes

Users

Not supported

Groups

Not supported

Standards activity

Plant SCADA component

Application Server

Notes

Labels

Imported

Any detected labels will be expanded out as they are imported into Application Server.

Styles

Not supported

Groups

Not supported

Fonts

Not supported

Setup activity

Plant SCADA component

Application Server

Notes

Alarm Categories

Not supported

Alarm Priorities

Priorities

Alarm Mode

Not supported

Cause and Response

Not supported

System Parameters

Not supported

Screen Profiles

Not supported

Devices

Not supported

Events

Not supported

Languages

Not supported

Keyboard Keys

Not supported

Custom Files

Not supported

In This Topic