Please ensure Javascript is enabled for purposes of website accessibility
Powered by Zoomin Software. For more details please contactZoomin

Plant SCADA

Support for expressions in QuickScript

  • Last UpdatedNov 03, 2026
  • 1 minute read

Any expressions in a Plant SCADA project will be converted to QuickScript when integrated into Application Server.

However, the conversion to QuickScript will not be successful if the following is detected.

  • A call to a Cicode function is detected in the expression.

    There is limited support for some Cicode functions that perform mathematical expressions (see the table below).

  • A syntax error is detected in an expression.

  • A syntax error is detected in a template expression.

  • Arrays are detected (they are not supported).

  • An unsupported format operator is detected.

  • An unsupported escape character is detected.

  • An unsupported template parameter reference is detected.

Note: Cicode expressions in alarm descriptions will not be converted to QuickScript.

The following table lists the Cicode functions that can be converted to QuickScript and describes how the conversions are performed.

Cicode

QuickScript

Abs

Abs

Sign

Sign

Min

System.Math.Min

Max

System.Math.Max

Pow

Converted to power operator.

For example:
x ** y

Sqrt

Sqrt

Exp

Exp

Log

Log10

Ln

Log

Pi

Pi

RadToDeg, DegToRad

Converted to equivalent expression. For example:

(rad * 180 / Pi())

(deg * Pi() / 180)

Sin, Cos, Tan

Sin, Cos, Tan

Arguments are automatically converted from radians to degrees.

For example:
Sin(x * 180 / Pi())

ArcSin, ArcCos, ArcTan

ArcSin, ArcCos, ArcTan

Return value is automatically converted from degrees to radians.

For example:
ArcSin(x) * Pi() / 180

IntToStr

StringFromIntg

The argument 'base' is automatically added with value 10.

RealToStr

StringFromReal

The Cicode arguments 'width' and 'separator' are not converted.