Determines which data columns to include in the results. This parameter is an integer representing a bit pattern where each bit represents a data column. If the bit is set to 1, the column is included in the results.

When you use this parameter with the wwHistory2 function, the bits are as follows (bit 0 is the rightmost bit):

Bit

Display option

Integer equivalent

18

wwStateCalc

262144

17

wwInterpolationType

131072

16

Value timestamp

65536

15

Show milliseconds in timestamp

32768

14

Quality

16384

13

OPC quality

8192

12

Quality detail

4096

11

wwRetrievalMode

2048

10

wwTagKey

1024

9

wwCycleCount

512

8

wwResolution

256

7

wwTimeDeadband

128

6

wwValueDeadband

64

5

wwTimestampRule

32

4

wwQualityRule

16

3

wwVersion

8

2

wwTimeZone

4

1

wwEdgeDetection

2

0

PercentGood

1

For additional information on each display option, see Display Options Tab.

To enable multiple display options, add up their integer equivalents and use the result as the value for this parameter. For example, if you want to use the wwHistory2 function and show the value timestamp with milliseconds as well as the history version, add the following values:

Bit

Display option

Integer equivalent

16

Value timestamp

65536

15

Show milliseconds in timestamp

32768

3

wwVersion

8

In this case, the parameter value is 98312 (65536 + 32768 + 8).