Quality rule - query 3

  • Last UpdatedFeb 07, 2025
  • 1 minute read

When you combine the same OPC quality then that OPC quality will be returned. However, when there is no good point in a cycle for cyclic modes such as Integral, Average, Counter, or AnalogSummary, the returned NULL value will have an OPC quality of 0 and a Quality Detail of 65536, regardless of combined qualities.

SELECT TagName, StartDateTime, EndDateTime, OPCQuality, PercentGood, wwRetrievalMode, first

FROM AnalogSummaryHistory

WHERE TagName = 'F0R5'

AND StartDateTime >= '2009-09-12 00:20'

AND EndDateTime <= '2009-09-12 00:40'

AND wwResolution = 10000

AND wwRetrievalMode = 'Cyclic'

If you run this query against the following sample data:

Tagname

DateTime

Resolution

QualityDetail

F0R5

2009-09-12 00:07

1.6

78

F0R5

2009-09-12 00:14

3.1

78

F0R5

2009-09-12 00:22

0.2

78

F0R5

2009-09-12 00:25

0.8

78

F0R5

2009-09-12 00:27

0.4

78

F0R5

2009-09-12 00:29

2.2

78

F0R5

2009-09-12 00:33

3.3

78

F0R5

2009-09-12 00:36

0.3

78

F0R5

2009-09-12 00:39

1.2

78

The results are:

Tagname

StartDate Time

EndDate Time

OPCQuality

PercentGood

wwRetrievalMode

first

F0R5

2009-09-12 00:20

2009-09-12 00:30

78

100

CYCLIC

0.200

F0R5

2009-09-12 00:30

2009-09-12 00:40

78

100

CYCLIC

3.300

TitleResults for “How to create a CRG?”Also Available in