Quality rule - query 2

  • Last UpdatedFeb 07, 2025
  • 1 minute read

Similar to Quality rule - query 1, if you combine a mixture of doubtful OPC qualities, a doubtful OPC quality (64) will be returned as the combined OPC quality.

SELECT TagName, DateTime, Value, QualityDetail, OPCQuality, wwRetrievalMode

FROM History

WHERE TagName = 'I0R5'

AND DateTime >= '2009-09-12 00:20'

AND DateTime <= '2009-09-12 00:40'

AND wwResolution = 10000

AND wwRetrievalMode = 'Integral'

If you run this query against the following sample data:

Tagname

DateTime

Resolution

QualityDetail

I0R5

2009-09-12 00:07

2

65

I0R5

2009-09-12 00:14

3

68

I0R5

2009-09-12 00:22

0

71

I0R5

2009-09-12 00:25

1

74

I0R5

2009-09-12 00:27

0

79

I0R5

2009-09-12 00:29

2

80

I0R5

2009-09-12 00:33

3

88

I0R5

2009-09-12 00:36

0

92

I0R5

2009-09-12 00:39

1

64

The results are:

Tagname

DateTime

Value

QualityDetail

OPCQuality

wwRetrievalMode

I0R5

00:20

26.0

64

64

INTEGRAL

I0R5

00:30

10.0

64

64

INTEGRAL

I0R5

00:40

16.0

64

64

INTEGRAL