AVEVA™ Communication Drivers

Supported hardware and software

  • Last UpdatedSep 16, 2024
  • 1 minute read

The MELSEC Communication Driver enables Ethernet and serial communication with Q, QnA, L, and the iQ-R-series PLCs from Mitsubishi Electric, using the MELSEC protocol.

To program these PLCs, you need to use the GX Developer, GX Works2, or GX Works3 programming software from Mitsubishi Electric.

Device Configuration

The support PLCs communicate over both UDP and TCP ports.

The Communication Method for:

  • Q-series PLCs is the MC protocol (MELSEC Communication Protocol)

  • iQ-R series PLCs is the SLMP protocol

    Notes: It is necessary to configure the Destination IP Address when communicating over UDP/IP.

Conformance

The following hardware and software was used for conformance testing of this Communication Driver.

Configuration:Q Series PLC (Ethernet)

  • Device: Q00JCPU with QJ71E71-100 module

  • Cable: Ethernet

  • UDP Port: 5000

  • TCP Port: 5002

Configuration: Q Series PLC (Serial)

  • Device: Q00JCPU with QJ71C24 module

  • Cable: Null Modem Cable with Gender Adapter

  • Serial Port: CH1 (RS232)

  • Comm Settings: 9600, 8, 1, Odd

Configuration: iQ-R Series PLC (Ethernet)

  • Device: R16SFCPU with Ethernet port embedded on the CPU

  • Cable: Ethernet

  • UDP Port: 3001

  • TCP Port: 5002