Special pre-configuration for S7-1200 and S7-1500 PLCs
- Last UpdatedSep 16, 2024
- 2 minute read
The SIDirect Legacy object requires some pre-configuration through the Siemens TIA portal to allow access to data inside the S7-1500 PLC. This pre-configuration consists of:
-
Enabling PUT/GET communication
-
Disabling optimized block access
Note: Pre-configuration is not required for the SIDirect Symbolic object.
Enable PUT/GET communication
-
In the navigation pane of the TIA software, locate the S7-1500 CPU.
-
Right-click the S7-1500 CPU and then click Properties. The properties dialog box appears.
-
In the left pane, click Protection.
-
Select the required access level for the PLC.
Note: If you select No Access, you will not be able to use the SIDirect Legacy object to access tags in the PLC.
-
In the Connection mechanisms area, select the Permit access with PUT/GET communication from remote partner check box.
Note: This field will be disabled if you select the access level as NO Access.
-
Click OK.
Disable optimized block access
-
In the TIA software, locate the data block in the left tree.
-
Right-click the data block, and then click Properties. The properties dialog box appears.
-
In the left pane, click Attributes.
-
Click to clear the Optimized block access check box.
-
Click OK.
If the legacy communication is still not established, perform the following steps:
1. Go offline.
2. Compile-hardware rebuild (all).
3. Download to the PLC.