Please ensure Javascript is enabled for purposes of website accessibility
Powered by Zoomin Software. For more details please contactZoomin

AVEVA™ Communication Drivers

Peripheral output bytes

  • Last UpdatedJul 29, 2024
  • 4 minute read

The following table summarizes the data format, item or point, suffix, data type, and range for Peripheral Input Bytes. See Conversions and suffixes of items (absolute addressing) for suffix definitions.

Data Format

Item/Point

Suffix

Data Type

Range

Bit

POx.y

PAx.y

PQx.y

POXx.y

PAXx.y

PQXx.y

VT_BOOL

VT_BOOL

VT_BOOL

VT_BOOL

VT_BOOL

VT_BOOL

0 or 1

0 or 1

0 or 1

0 or 1

0 or 1

0 or 1

String

POSx.v

PASx.v

PQSx.v

POSTRINGx.v

PASTRINGx.v

PQSTRINGx.v

VT_BSTR

VT_BSTR

VT_BSTR

VT_BSTR

VT_BSTR

VT_BSTR

String

String

String

String

String

String

Byte

POBx

PABx

PQBx

POBYTEx

PABYTEx

PQBYTEx

DT

VT_UI1

VT_UI1

VT_UI1

VT_UI1

VT_UI1

VT_UI1

VT_BSTR

0 to 255

0 to 255

0 to 255

0 to 255

0 to 255

0 to 255

1990-1-1-0:00:00.000 to 2089-12-31-23:59:59.999

Byte Array

POBx.v

PABx.v

PQBx.v

POBYTEx.v

PABYTEx.v

PQBYTEx.v

VT_ARRAY|VT_UI1

VT_ARRAY|VT_UI1

VT_ARRAY|VT_UI1

VT_ARRAY|VT_UI1

VT_ARRAY|VT_UI1

VT_ARRAY|VT_UI1

0 to 255 for each element*

0 to 255 for each element*

0 to 255 for each element*

0 to 255 for each element*

0 to 255 for each element*

0 to 255 for each element*

USINT

D<B,I>d,USINTx

DT

VT_UI1

VT_BSTR

0 to 255

1990-1-1-0:00:00.000 to 2089-12-31-23:59:59.999***

USINT Array

D<B,I>d,USINTx,v

VT_ARRAY|VT_UI1

0 to 255 for each element*

Char

PACHARx

POCHARx

PQCHARx

DT

VT_I1

VT_I1

VT_I1

VT_BSTR

-128 to 127

-128 to 127

-128 to 127

1990-1-1-0:00:00.000 to 2089-12-31-23:59:59.999

Char Array

POCHARx.v

PACHARx.v

PQCHARx.v

VT_ARRAY|VT_I1

VT_ARRAY|VT_I1

VT_ARRAY|VT_I1

0 to 255

0 to 255

0 to 255

0 to 255

0 to 255

0 to 255

1990-1-1-0:00:00.000 to 2089-12-31-23:59:59.999

SINT

D<B,I>d,SINTx

DT

VT_I1

VT_BSTR

-128 to 127

1990-1-1-0:00:00.000 to 2089-12-31-23:59:59.999***

SINT Array

D<B,I>dSINTx,v

VT_ARRAY|VT_UI1

-128 to 127 for each element*

Word

POWn

PAWn

PQWn

POWORDn

PAWORDn

PQWORDn

BCD

KT

S5T

TR

D

VT_UI2

VT_UI2

VT_UI2

VT_UI2

VT_UI2

VT_UI2

VT_UI2

VT_BSTR

VT_BSTR

VT_R4

VT_BSTR

0 to 65535

0 to 65535

0 to 65535

0 to 65535

0 to 65535

0 to 65535

0 to 9999

0.0 to 999.3

0ms to 2h46m30s0ms

0.0 to 9990.0 (s)

1990-1-1 to 2168-12-31

Word Array

POWn,v

PAWn,v

PQWn,v

POWORDn,v

PAWORDn,v

PQWORDn,v

T_ARRAY|VT_UI2

VT_ARRAY|VT_UI2

VT_ARRAY|VT_UI2

VT_ARRAY|VT_UI2

VT_ARRAY|VT_UI2

VT_ARRAY|VT_UI2

0 to 65535 for each element*

0 to 65535 for each element*

0 to 65535 for each element*

0 to 65535 for each element*

0 to 65535 for each element*

0 to 65535 for each element*

UINT

D<B,I>d,UINTn

BCD

KT

S5T

TR

D

VT_UI2

VT_UI2

VT_BSTR

VT_BSTR

VT_R4

VT_BSTR

0 to 65535

0 to 9999***

0.0 to 999.3***

0ms to 2h46m30s0ms***

0.0 to 9990.0 (s)***

1990-1-1 to 2168-12-31

UINT Array

D<B,I>d,UINTn,v

VT_ARRAY|VT_UI2

0 to 65535 for each element*

Integer

POINTn

PAINTn

PQINTn

BCD

D

VT_I2

VT_I2

VT_I2

VT_I2

VT_BSTR

-32768 to 32767

-32768 to 32767

-32768 to 32767

-999 to 999

1990-1-1 to 2168-12-31

Integer Array

POINTn,v

PAINTn,v

PQINTn,v

VT_ARRAY|VT_I2

VT_ARRAY|VT_I2

VT_ARRAY|VT_I2

-32768 to 32767 for each element*

-32768 to 32767 for each element*

-32768 to 32767 for each element*

Double Word

PODm

PADm

PQDm

PODWORDm

PADWORDm

PQDWORDm

BCD

TOD

T

VT_UI4

VT_UI4

VT_UI4

VT_UI4

VT_UI4

VT_UI4

VT_UI4

VT_BSTR

VT_BSTR

0 to 4294967295**

0 to 4294967295**

0 to 4294967295**

0 to 4294967295**

0 to 4294967295**

0 to 4294967295**

0 to 99999999

0:00:00.000 to 23:59:59.999

-24D_20H_31M_23S_648MS to 24D_20H_31M_23S_647MS

Double Word Array

PODm,v

PADm,v

PQDm,v

VT_ARRAY|VT_UI4

VT_ARRAY|VT_UI4

VT_ARRAY|VT_UI4

0 to 4294967295 for each element*

0 to 4294967295 for each element*

0 to 4294967295 for each element*

UDINT

D<B,I>d,UDINTm

BCD

TOD

T

VT_UI4

VT_UI4

VT_BSTR

VT_BSTR

0 to 4294967295**

0 to 99999999***

0:00:00.000 to 23:59:59.999

-24D_20H_31M_23S_648MS to 24D_20H_31M_23S_647MS

UDINT Array

D<B,I>d,UDINTm,v

VT_ARRAY|VT_UI4

0 to 4294967295 for each element*

Double Integer

PODINTm

PADINTm

PQDINTm

BCD

TOD

T

VT_I4

VT_I4

VT_I4

VT_I4

VT_BSTR

VT_BSTR

-2147483648 to 2147483647

-2147483648 to 2147483647

-2147483648 to 2147483647

-9999999 to 9999999

0:00:00.000 to 23:59:59.999

-24D_20H_31M_23S_648MS to 24D_20H_31M_23S_647MS

Double Integer Array

PODINTm,v

PADINTm,v

PQDINTm,v

VT_ARRAY|VT_I4

VT_ARRAY|VT_I4

VT_ARRAY|VT_I4

-2147483648 to 2147483647 for each element*

-2147483648 to 2147483647 for each element*

-2147483648 to 2147483647 for each element*

Real

POREALm

PAREALm

PQREALm

VT_R4

VT_R4

VT_R4

+/-1.2e-38 to +/-3.4e+38

+/-1.2e-38 to +/-3.4e+38

+/-1.2e-38 to +/-3.4e+38

Real Array

POREALm,v

PAREALm,v

PQREALm,v

VT_ARRAY|VT_R4

VT_ARRAY|VT_R4

VT_ARRAY|VT_R4

+/-1.2e-38 to +/-3.4e+38 for each element*

+/-1.2e-38 to +/-3.4e+38 for each element*

+/-1.2e-38 to +/-3.4e+38 for each element*

*: For DDE/SuiteLink, the item value is the Hex ASCIi representation of the complete array. The result is one string containing all the elements of the array in the Hex ASCIi representation of the binary data in big-endian format when data is returned to the DDE/SuiteLink layer.

**: For DDE/SuiteLink, this value is restricted to the range of 0 to 2147483647. Values higher than that are clamped to the maximum value of 2147483647 in a SuiteLink or DDE client. In this case, the quality of the item shows "Clamp High."

Where:

x

is the start address, with a range from 0 to 65535.

y

is the bit position, with a range from 0 to 7.

0 is the LSB (Least Significant Bit).

7 is the MSB (Most Significant Bit).

n

is the start address of 2-byte data/2-byte data arrays, with a range from 0 to 65534.

m

is the start address of 4-byte data/4-byte data arrays, with a range from 0 to 65532.

v

is the length of data in elements (an item in an array), with a range from 1 to (net PDU data size/type size - header information).

***: The Communication Driver provides suffixes (S5T, TR, DT, KT, and BCD) that are used to interpret raw bytes as having a special data format. Review the PLC processor documentation, as not all processors have ladder logic internally to interpret those data formats the same way (for example, the S7-1200 PLC).

Note: All peripheral outputs are Write-Only. The longest string or array that can be read in a cyclic service is the length of the PDU size minus 32 bytes. The longest string the InTouch software can process is 131 bytes. The longest string that can be poked is 256 bytes or the PDU size minus 28 bytes, whichever is less. All output modules are not readable. Only POKES are allowed.