PLC-5 item naming

  • Last UpdatedAug 29, 2024
  • 2 minute read

The general format of item names for data from the PLC-5 controllers matches the naming convention used by the programming software. The following is the format:

[$] X [file] : element [.field] [/bit]

Note: The parts of the name shown in square brackets ([]) are optional.

Item Name

Description

$

Purely optional.

X

Identifies the file type.

The following table summarizes the valid file types, the default file number for each type, and the fields allowed (if any).

file

File number (0 - 999 decimal).

  • File 0 must be Output.

  • File 1 must be Input.

  • File 2 must be Status.

element

Element number within the file.

  • For Input and Output files it is also called rack-and-group number and must be 0 - 777 octal.

  • For all other file types, it must be 0 - 999 decimal.

.field

Valid only for Counter, Timer, ASCII String, PID, SFC Status, Block Transfer, and Control files.

Refer to the following table.

/bit

Valid for all file types except ASCII String and Floating Point.

  • For Input and Output files it must be 0 - 17 octal.

  • For all other file types it must be 0 - 15 decimal.

Identifier

File Type

Default File #

.fields

O

Output

0

N/A

I

Input

1

N/A

S

Status

2

N/A

B

Binary

3

N/A

T

Timer

4

.PRE .ACC .EN .TT .DN

C

Counter

5

.PRE .ACC .CU .CD .DN .OV .UN

R

Control

6

.LEN .POS .EN .EU .DN .EM .ER .UL .IN .FD

N

Integer

7

N/A

F

Floating Point

8

N/A

A

ASCII

None

N/A

D

BCD

None

N/A

ST

ASCII String*

None

.LEN

PD

PID*

None

.ADRF .ADRE .BIAS .CA .CL .CT .DB .DO .DVDB .DVN .DVNA .DVP .DVPA .EN .ERR .EWD .INI .KD .KI .KP .MAXI .MAXO .MAXS .MINI .MINO .MINS .MO .OLH .OLL .OUT .PE .PV .PVDB .PVH .PVHA .PVL .PVLA .PVT .SO .SP .SPOR .SWM .TIE .UPD

SC

SFC Status*

None

.DN .ER .FS .LS .OV .PRE .SA .TIM

BT

Block Transfer* (Read-Only)

None

.EN .ST .DN .ER .CO .EW .NR .RW .TO .RLEN .DLEN .FILE .ELEM

MG

Message

None

.NR .TO .EN .ST .DN .ER .CO .EW .ERR .RLEN .DLEN .DATA[0] through .DATA[51]

CT

CNet Message

None

.TO .EW .CO .ER .DN .ST .EN .ERR .RLEN .DLEN .FILE .ELEM

* Available only on certain PLC-5 models. Check the Processor Manual for the model being used.