Life Safety Zone (LSZ)
- Last UpdatedDec 08, 2020
- 2 minute read
Supported properties of the Life Safety Zone object (LSZ)
|
Property |
Value Format |
Example |
|
OBJECT-IDENTIFIER |
String [ObjectNumber]: [Instance Number] |
1:0 |
|
OBJECT-NAME |
String |
temperatureSensor_core |
|
OBJECT-TYPE |
Integer |
0 |
|
PRESENT-VALUE |
Float |
123.2 |
|
TRACKING-VALUE |
Float(0–23) |
Reflects the non-latched state of the Life Safety Point object |
|
DESCRIPTION |
String |
This sensor monitors the core activity |
|
DEVICE-TYPE |
String |
This is a text description of the physical device that the Life Safety Point object represents |
|
STATUS-FLAGS |
4 Boolean values(1=true,0=false) encoded as string {IN_ALARM, FAULT, OVERRIDDEN, OUT_OF_SERVICE} |
1010 |
|
EVENT-STATE |
Integer |
0 |
|
RELIABILITY |
Integer |
0 |
|
OUT-OF-SERVICE |
Boolean |
0 |
|
MODE |
Integer(0–14) |
Shall convey the desired operating mode for the Life Safety Point object |
|
ACCEPTED-MODES TIME-DELAY |
String Integer |
Shall specify all values the Mode property accepts when written to using BACnet services. For example: 10|20|30|40|… 0 |
|
NOTIFICATION-CLASS |
Integer |
0 |
|
LIFE-SAFETY-ALARM-VALUES |
String |
This property is required if intrinsic reporting is supported by this object. |
|
ALARM-VALUES |
List of unsigned integers separated by pipes (|) and encoded as a string |
1|2|3 |
|
FAULT-VALUES |
List of unsigned integers separated by pipes (|) and encoded as a string |
1|2|3 |
|
EVENT-ENABLE |
3 Boolean values (1 = true, 0 = false) encoded as a string {to-offnormal, to- fault, to-normal} 3 Boolean values (1 = true, 0 = false) encoded as a string {to-offnormal, to- fault, to-normal} |
101 |
|
ACKED-TRANSITIONS |
101 |
|
|
NOTIFY-TYPE |
Integer |
1 |
|
EVENT-TIME-STAMPS |
Sequence of time stamps encoded as a string |
2|1-1-197011:0:0.0;2|1-1-197011:0:0.0;2|1-1-197011:0:0.0 |
|
SILENCED |
Unsigned Integer(0–3) |
Indicates the silenced state. |
|
OPERATION-EXPECTED |
Unsigned Integer(0–9) |
Specifies the next operation expected by this object to handle a specific life safety situation |
|
MAINTENANCE-REQUIRED ZONE-MEMBERS |
Unsigned Integer(0–3) List separated by pipes(|)and encoded as a string |
Indicates the type of maintenance required for the life safety point. (0:1,0:2|0:3,0:4|0:5,0:6|...) |
|
MEMBER-OF |
List separated by pipes(|)and encoded as a string |
Shall indicate those Life Safety Zone objects of which this Life Safety Point object is considered to be a zone member. For example: 0:1,0:2|0:3,0:4|0:5,0:6|… |
|
PROFILE-NAME |
String |
test |