Please ensure Javascript is enabled for purposes of website accessibility
Powered by Zoomin Software. For more details please contactZoomin

AVEVA™ Communication Drivers

2023 R2 SP1 P02

  • Last UpdatedJul 10, 2025
  • 2 minute read

Patch Installation

Communication Drivers Pack 2023 R2 SP1 Patch 02 is a component of the System Platform 2023 R2 SP1 Patch 02 release. CDP 2023 R2 SP1 P02 can be installed only on nodes that have CDP 2023 R2 SP1 P01 or CDP 2023 R2 SP1.

For more information on installing the patch, refer to the System Platform Patch Install readme.

Important: The Communication Drivers Pack online help files and AVEVA Help Viewer will not be included or supported in future releases. All product documentation will continue to be available in PDF format on the installation media and on the web at docs.aveva.com.

Resolved Issues

This section contains a list of all the defects and issues that have been resolved in a Communication Driver in the CDP 2023 R2 SP1 P02 release.

Communication Drivers Core

Defect ID

Case Number

Description

3805118

960524391

Microsoft Management Console (MMC) would repeatedly crash.

3723683

960538551

The View.exe application would hang repeatedly after migrating to CDP 2023 R2 SP1 due to a deadlock.

3864132

960560032

The datetime value returned from a Gateway OPC UA connection did not include milliseconds.

3942846

960604144

Communication Drivers would crash due to an issue while converting NaN values to Float.

(Internal)

N/A

Fixed the upgrade issue in which the configuration set of a Communication Driver is reset to the default configuration set, instead of retaining the existing configuration set before the upgrade.

Gateway

Defect ID

Case Number

Description

3630017

960455462

If a minimum of one invalid item was present during a read transaction to ArchestrA, it would cause all other valid items to get bad quality. This was caused due to the longer waiting time for an invalid item which resulted in a transaction timeout.

3683666

960510868

[OPC UA][Enhancement] In runtime, a read request was not sent immediately after a write operation is performed, which resulted in slower performance.

3814765

960565512

The Gateway Communication Driver was crashing often after an upgrade due to the way in which item counts were handled.

3870511

960576959

When adding items in the OPC Client, the first item (client handle 0x00) would not get updated, while all other items would function as expected.

3804935, 3844400

960563100

[OPC UA] When calling a method, array input arguments were incorrectly parsed as strings by the Gateway Communication Driver, causing the driver to crash.

3907407

960585095

[Enhancement] The retain flag option has been added to Gateway Communication Driver configuration.

3888724

960581935

[OPC UA] When calling a method, the Gateway Communication Driver was unable to read values from the OPC UA server when the method call returned uncertain values.

3889868

960589754

[OPC UA] An OPC UA methods call would not be sent if there were no dimensions in an array argument.

MBTCP

Defect ID

Case Number

Description

3800677

960550705

The "Swap Byte" option in the MBTCP configuration settings did not function as expected.

SIDIRECT

Defect ID

Case Number

Description

3786398

960555732

Default Poke Mode settings did not affect Legacy connections.

Known Issues

There are no known issues in this specific release of the Communication Drivers Pack.