Suffix S5T
- Last UpdatedJun 03, 2020
- 1 minute read
All items with the following data format and suffix S5T are converted from S5T to a message and back to store a value in the range of 0ms to 2h46m30s.
-
Word
The memory in the PLC is exactly the same as for the KT items, but the presentation is different, although the meaning is the same. This means a memory content of 0x3999 (as in the example for KT) results in the string of 2h46m30s0ms.
The meaning of 999.3 (KT) is:
|
999 |
The first three characters are the time value in BCD. |
|
3 |
The last digit is the multiplier. Possible values are: |
This means:
|
A value of 123.0 represents: |
123*0.01s=1.23s (equals 1s230ms) |
|
A value of 543.2 represents: |
543*1s=543s (equals 9m3s0ms) |
|
A value of 999.3 represents: |
999*10s=9990s (equals 2h46m30s0ms) |