Please ensure Javascript is enabled for purposes of website accessibility
Powered by Zoomin Software. For more details please contactZoomin

AVEVA™ Communication Drivers

Suffix S5T

  • Last UpdatedJun 03, 2020
  • 1 minute read

All items with the following data format and suffix S5T are converted from S5T to a message and back to store a value in the range of 0ms to 2h46m30s.

  • Word

The memory in the PLC is exactly the same as for the KT items, but the presentation is different, although the meaning is the same. This means a memory content of 0x3999 (as in the example for KT) results in the string of 2h46m30s0ms.

The meaning of 999.3 (KT) is:

999

The first three characters are the time value in BCD.

3

The last digit is the multiplier. Possible values are:
0: 0.01s
1: 0.1s
2: 1s
3: 10s.

This means:

A value of 123.0 represents:

123*0.01s=1.23s (equals 1s230ms)

A value of 543.2 represents:

543*1s=543s (equals 9m3s0ms)

A value of 999.3 represents:

999*10s=9990s (equals 2h46m30s0ms)

TitleResults for “How to create a CRG?”Also Available in