Please ensure Javascript is enabled for purposes of website accessibility
Powered by Zoomin Software. For more details please contactZoomin

AVEVA™ Communication Drivers

Binary Output (BO)

  • Last UpdatedDec 08, 2020
  • 2 minute read

Supported properties of the Binary Output object (BO)

Property

Value Format

Example

OBJECT-IDENTIFIER

OBJECT-NAME

String

[ObjectNumber]: [Instance Number]

String

1:0

temperatureSensor_core

OBJECT-TYPE

Integer

0

PRESENT-VALUE

Integer

123

DESCRIPTION

String

This sensor monitors the core activity

DEVICE-TYPE

Integer

5

STATUS-FLAGS

4 Boolean values (1 = true, 0 = false) encoded as string

{IN_ALARM, FAULT, OVERRIDDEN, OUT_OF_SERVICE}

1010

EVENT-STATE

Integer

0

RELIABILITY

Integer

0

OUT-OF-SERVICE

Integer

0

POLARITY

Integer(normal=0,reverse=1)

1

INACTIVE-TEXT

String

test

ACTIVE-TEXT

String

Test

CHANGE-OF-STATE-TIME

Date and Time separated by a space character and encoded as a string. For more information look at BACnetDateTime type in the Data Type section.

23-8-20119:42:44.64

CHANGE-OF-STATE-COUNT

UnsignedInteger

33

TIME-OF-STATE-COUNT-RESET

Date and Time separated by a space character and encoded as a string. For more information look at BACnetDateTime type in the Data Type section.

23-8-20119:42:44.64

ELAPSED-ACTIVE-TIME

Unsigned Integer

12

TIME-OF-ACTIVE-TIME-RESET

Date and Time separated by a space character and encoded as a string. For more information look at BACnetDateTime type in the Data Type section.

23-8-20119:42:44.64

MINIMUM-OFF-TIME

Integer

0

MINIMUM-ON-TIME

Integer

0

PRIORITY-ARRAY

Sequence of 16 values separated by pipes (|) and encoded as a string. The type of these values can be one of the following (Null, real, binary, integer). For more information, see BACnetPriorityArray

NULL|NULL|NULL|NULL|NULL|NULL|12|NULL| NULL|NULL|NULL|NULL|NULL|NULL|NULL|25.000000

RELINQUISH-DEFAULT

Real

12.3

TIME-DELAY

Integer

0

NOTIFICATION-CLASS

Integer

0

FEEDBACK-VALUE

Integer(inactive=0,active=1)

1

EVENT-ENABLE

3 Boolean values (1 = true, 0 = false) encoded as a string

{to-offnormal, to- fault, to-normal}

101

ACKED-TRANSITIONS

3 Boolean values (1 = true, 0 = false) encoded as a string

{to-offnormal, to- fault, to-normal}

101

NOTIFY-TYPE

Integer

1

EVENT-TIME-STAMPS

Sequence of time stamps encoded as a string

2|1-1-197011:0:0.0;2|1-1-197011:0:0.0;2|1-1-197011:0:0.0

PROFILE-NAME

String

Test

TitleResults for “How to create a CRG?”Also Available in