AVEVA™ Communication Drivers

BACnetPriorityArray

  • Last UpdatedJan 21, 2022
  • 1 minute read

The BacnetPriorityArray data type is represented as an array of 16 priority values. This Communication Driver supports NULL values and unsigned values on these fields.To write on a priority array data type you must write a Present-Value specifying the priority. The read operations can be performed directly on the property of this type.

The format for displaying this datatype is:

<Value for Priority1>|< Value for Priority2>|< Value for Priority3>|. . .|< Value for Priority16>

Example:

5|1|30|0|0|0|0|0|0|0|0|0|0|0|0|0

The meaning of each priority level is described on the table below.

Priority Level

Application

1

Manual-Life Safety

2

Automatic-Life Safety

3

Available

4

Available

5

Critical Equipment Control

6

Minimum On/Off

7

Available

8

Manual Operator

9

Available

10

Available

11

Available

12

Available

13

Available

14

Available

15

Available

16

Available