Logix5000 error codes

  • Last UpdatedSep 12, 2024
  • 3 minute read

The Logix5000 processor generates error conditions. The following tables show these errors and the server-specific strings generated by the Communication Driver to the logger.

Note: All of the error messages shown in the following table apply to the DASProtFail log flag.

General Allen-Bradley Error Code (High byte = 00)

Logger Message

00

Success

01

Connection failed

02

Insufficient Connection Manager resources

03

Invalid connection number

04

IOI could not be deciphered. Either it was not formed correctly or the match tag does not exist

05

The particular item referenced could not be found

06

The amount of data requested would not fit into the response buffer. Partial data transfer has occurred.

07

Connection has been lost

08

Requested service not supported

09

Error in data segment or invalid attribute number

0A

An error has occurred trying to process one of the attributes

0C

Service cannot be performed while object is in current state

10

Service cannot be performed while device is in current state

11

Response data too large

13

Not enough command data/parameters were supplied in the command to execute the service requested

14

Attribute not supported

15

Too much data was received

1C

An insufficient number of attributes were provided compared to the attribute count

1E

Errors encountered with the items in the message

26

The IOI word length did not match the amount of IOI which was processed

None of the above codes

Unknown Status

Extended Allen-Bradley Error Code (Hex)

Logger Message

2104

The beginning offset was beyond the end of the template.

2105

You have tried to access beyond the end of the data object.

2106

Data in use.

2107

The abbreviated type does not match the data type of the data object.

0100

Connection in Use or Duplicate Forward Open.

0103

Transport Class and Trigger combination not supported.

0106

Ownership Conflict.

0107

Connection not found at target application.

0108

Invalid Connection Type. Indicates a problem with either the Connection Type or Priority of the Connection.

0109

Invalid Connection Size.

0110

Device not configured

0111

RPI not supported. May also indicate problem with connection time-out multiplier.

0113

Connection Manager cannot support any more connections.

0114

Either the Vendor ID or the Product Code in the key segment did not match the device.

0115

Product Type in the key segment did not match the device.

0116

Major or Minor Revision information in the key segment did not match the device.

0117

Invalid Connection Point.

0118

Invalid Configuration Format.

0119

Connection request fails since there is no controlling connection currently open.

011A

Target Application cannot support any more connections.

011B

RPI is smaller than the Production Inhibit Time.

0203

Connection cannot be closed since the connection has timed out.

0204

Unconnected Send timed out waiting for a response.

0205

Parameter Error in Unconnected Send Service.

0206

Message too large for Unconnected message service.

0207

Unconnected acknowledge without reply.

0301

No buffer memory available.

0302

Network Bandwidth not available for data.

0303

No Tag filters available.

0304

Not Configured to send real-time data.

0311

Port specified in Port Segment Not Available.

0312

Link Address specified in Port Segment Not Available.

0315

Invalid Segment Type or Segment Value in Path.

0316

Path and Connection not equal in close.

0317

Either Segment not present or Encoded Value in Network Segment is invalid.

0318

Link Address to Self Invalid.

0319

Resources on Secondary Unavailable.

031A

Connection already established.

031B

Direct connection already established.

031C

Miscellaneous.

031D

Redundant connection mismatch.

None of the above codes

Unknown Extended Status.

Note: For more information about the general and extended Allen-Bradley error codes, please refer to the Allen-Bradley controller documentation.