SLC500_DHP object
- Last UpdatedAug 29, 2024
- 1 minute read
The SLC500_DHP object represents the physical Allen-Bradley SLC500 processor on the Data Highway Plus network.
-
1747-L54x
This object is hosted by PORT_DHP.
Add the SLC500_DHP object to your ABCIP hierarchy
-
Select and right-click on the New_PORT_DHP_000 object.
-
Select Add SLC500_DHP Object from the shortcut menu. The New_SLC500_DHP_000 object is created.
-
Rename the newly created object as appropriate. The SLC500_DHP Parameters configuration view is displayed.
The configuration view contains three parameters, two of which are configurable:
-
Processor Type: (not configurable) The information is automatically provided (SLC500).
-
DH Plus Node Address: The node address on the DH+ network (Octal). Select the DH+ node number from the drop-down box.
-
The valid range is 0 - 77 octal.
-
The default value is 0 (zero) octal.
-
-
Reply Timeout: Enter the maximum amount of time (in seconds) that the Communication Driver will wait for a response from the controller.
-
The valid range is 1 - 300 seconds.
-
The default value is 15 seconds.
-