AVEVA™ Operations Management Interface

About limit alarm checking

  • Last UpdatedJul 18, 2024
  • 1 minute read

Generic limit checking done for all high limit alarms are:

  • If PV > Limit, then record Time and Current PV, set the alarm condition, and send the alarm notification.

  • If PV <= Limit – ValueDeadband, then clear the condition and send the notification of the clear.

Generic limit checking for low limit alarms:

  • If PV < Limit, then record the Time and Current PV, set the alarm condition, and send the alarm notification.

  • If PV >= Limit + ValueDeadband, then clear the condition and send the notification of the clear.